0.6/1kv Single Core XLPE Insulation PVC Bedded Aluminium Wire Armour PVC Sheath Power Cable
CU/XLPE/PVC/AWA/PVC (Single Core)
XLPE Insulated, PVC Bedded, Alminium Wire Armoured, PVC Sheathed Cable
Application
These power cable for fixed installations such as distribution networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.
Armoured cable suitable for direct burial.
Construction
Conductor: Plain annealed copper, class1 solid or class 2 stranded acc. to IEC 60228.
Flexible class 5 or tinned conductor could be offer upon request.
Insulation: Cross-linked polyethlene (XLPE) compound as per IEC 60502-1.
Insulation Color Code:
Number of Cores | Color Code to IEC 60502-1 | Color Code to BS 5467 |
1 | Red or Black | Brown or Blue |
Bedding: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1.
Bedding Colour: Black or other color as per customer request.
Armour: Aluminium wire armoured (AWA).
Outer Sheath: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1.
Outer Sheath Color: Black or other color as per customer request.
Electrical Characteristics
Recommended rated voltages U0
Highest system voltage (Um) (kV) |
Rated voltage (U0) (kV) | |
Categories A and B | Category C | |
1,2 | 0,6 | 0,6 |
Routine test voltages
Rated voltage U0 (kV) | 0,6 |
Test voltage (kV) | 3,5 |
Maximum conductor temperatures for different types of insulating compound
Maximum conductor temperature (°C) | |
Normal operation | Short-circuit (5 s maximum duration) |
90 | 250 |
Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes
Installation Reference
Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 50
Reference Standards
Design Specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1
Dimension
Nominal Conductor Area (mm2) |
No,and Diameter of Wires (no./mm) |
Thickness of Insulation (mm) |
Thickness of Bedding (mm) |
Diameter of Armour Wire (mm) |
Thickness of Sheath (mm) |
Overall Diameter (mm) |
Approximate Weight (kg/km) |
1x50 | 19/1.78 | 1 | 1 | 1.25 | 1.8 | 19 | 1086 |
1x70 | 19/2.14 | 1.1 | 1 | 1.25 | 1.8 | 21 | 1387 |
1x95 | 19/2.52 | 1.1 | 1 | 1.6 | 1.8 | 23.6 | 1881 |
1x120 | 37/2.03 | 1.2 | 1 | 1.6 | 1.8 | 25.4 | 2227 |
1x150 | 37/2.25 | 1.4 | 1 | 1.6 | 1.8 | 27.4 | 2611 |
1x185 | 37/2.52 | 1.6 | 1 | 1.6 | 1.9 | 29.8 | 3132 |
1x240 | 61/2.25 | 1.7 | 1 | 2 | 2 | 33.7 | 4131 |
1x300 | 61/2.52 | 1.8 | 1.2 | 2 | 2.1 | 36.9 | 4988 |
1x400 | 61/2.85 | 2 | 1.2 | 2 | 2.2 | 40.5 | 6091 |
1x500 | 61/3.20 | 2.2 | 1.2 | 2.5 | 2.4 | 45.4 | 7823 |
1x630 | 127/2.52 | 2.4 | 1.4 | 2.5 | 2.5 | 50.4 | 9702 |
1x800 | 127/2.85 | 2.6 | 1.4 | 2.5 | 2.7 | 55.5 | 11924 |
1x1000 | 127/3.20 | 2.8 | 1.6 | 2.5 | 2.9 | 61.2 | 14606 |