Multi-cores Galvanised Steel Wire Armoured SWA 0.6/1KV Low Voltage Power Cable

Multi-cores Galvanised Steel Wire Armoured SWA 0.6/1KV Low Voltage Power Cable

 

CU/XLPE/PVC/SWA/PVC (Multi - Cores)
XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable

 

Application

These power cable for fixed installations such as distribution networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.
Armoured cable suitable for direct burial.

multi core insulation sheath swa sheath

Construction

Conductor: Plain annealed copper, class1 solid or class 2 stranded acc. to IEC 60228.
Flexible class 5 or tinned conductor could be offer upon request.
Insulation: PCross-linked polyethlene (XLPE) compound as per IEC 60502-1.
Insulation Color Code:

Number of Cores Color Code to IEC 60502-1 Color Code to BS 5467
6 and above White with Black
Numbering or Others
White with Black
Numbering or Others

Assembly: Cores cabled together with PP filler and covered with non-woven tape.
Bedding: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1.
Bedding Colour: Black or other color as per customer request.
Armour: Galvanized steel wire armoured (SWA).
Outer Sheath: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1.
Outer Sheath Color: Black or other color as per customer request.

 

Electrical Characteristics

Recommended rated voltages U0

Highest system voltage
(Um) (kV)
Rated voltage (U0) (kV)
Categories A and B Category C
1,2 0,6 0,6

Routine test voltages

Rated voltage U0 (kV) 0,6
Test voltage (kV) 3,5

Maximum conductor temperatures for different types of insulating compound

Maximum conductor temperature (°C)
Normal operation Short-circuit (5 s maximum duration)
90 250

Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes

 

Installation Reference

Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 70

 

Reference Standards

Design Specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1

 

Dimension

No.of Cores Nominal Conductor Area
(mm2)
No,and Diameter of Wires
(no./mm)
Thickness
of Insulation
(mm)
Thickness of Bedding
(mm)
Diameter of Armour Wire
(mm)
Thickness of Sheath
(mm)
Overall Diameter
(mm)
Approximate Weight
(kg/km)
5 1.5        7/0.53 0.7 1 1.25 1.8 16.2 573
7 7/0.53 0.7 1 1.25 1.8 17.1 652
10 7/0.53 0.7 1 1.25 1.8 20.1 835
12 7/0.53 0.7 1 1.25 1.8 20.5 896
19 7/0.53 0.7 1 1.6 1.8 23.8 1294
20 7/0.53 0.7 1 1.6 1.8 24.2 1337
24 7/0.53 0.7 1 1.6 1.8 26.7 1541
37 7/0.53 0.7 1 1.6 1.9 29.9 1975
5 2.5        7/0.67 0.7 1 1.25 1.8 17.3 671
7 7/0.67 0.7 1 1.25 1.8 18.3 775
10 7/0.67 0.7 1 1.6 1.8 22.4 1145
12 7/0.67 0.7 1 1.6 1.8 23 1233
19 7/0.67 0.7 1 1.6 1.8 25.9 1591
20 7/0.67 0.7 1 1.6 1.8 26.4 1648
24 7/0.67 0.7 1 1.6 1.8 29.3 1911
37 7/0.67 0.7 1.2 2 2 34.3 2814
5 4        7/0.85 0.7 1 1.25 1.8 18.8 812
7 7/0.85 0.7 1 1.25 1.8 20 956
10 7/0.85 0.7 1 1.6 1.8 24.6 1413
12 7/0.85 0.7 1 1.6 1.8 25.2 1538
19 7/0.85 0.7 1 1.6 1.8 28.6 2035
20 7/0.85 0.7 1 1.6 1.8 29.2 2112
24 7/0.85 0.7 1 2 1.8 33.3 2710
37 7/0.85 0.7 1.2 2 1.8 37.7 3609

 

downloadpdf