Multi Pairs, Individual&Collective Screen, LSZH Sheathed

Application

Suitable for connecting instruments and control systems for analogue or digital signal transmission. Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations

Construction

InstrumentationCable 1

Conductor: Solid, stranded or flexible plain or metal coated copper in accordance with class1, 2 or 5 of  
HD383 in the range of 0.5mm2 to 1.5mm2.  
Insulation: PE or XLPE to EN 50290. Suitable alternative materials are under consideration.  

Pair Identification: Black&White color with number on the cores for multi pairs, start with 1 in the centre.

Individual Screen: Aluminimum foil tape over a tinned copper drain wire.

Wrapping:                 At least 1 layer of plastic tape.

Collective Screen: Aluminimum foil tape over a tinned copper drain wire.

Outer Sheath:           Halogen free flame retardant compound LSZH, to EN 50290-2-27.

Electrical data at 20°C

 
Character
Unit     Values  
Conductor size nom. mm² 0.5 0.75   1.0 1.5
Conductor resistance max. Ω/km 36.7 25.0   18.5 12.3
Insulation resistance min. MΩ x km     5000  
L/R (ratio) max. µH/Ω   25     40
Inductance max. mH/km     1  
Mutual capacitance max. nF/m   115     115
Capacitance unbalance max. pF/500 m     500  
Test voltage   V     1500  
Operating voltage U0 / U max. V     300  

 

Technical Data

Temperature range (during operation): -30°C to 70°C for PE insulation and -30°C to 90°C for XLPE insulation.

Temperature range (during installation): -5°C to 50°C

Min. bending radius: 7.5 x cable Ø

downloadpdf