Suitable for connecting instruments and control systems for analogue or digital signal transmission.

Application

Suitable for connecting instruments and control systems for analogue or digital signal transmission. Recommended for direct burial, especially in presence of oil and aggressive chemical substances

Construction

InstrumentationCable 15

Conductor: Solid, stranded or flexible plain or metal coated copper in accordance with class1, 2 or 5 of  
HD383 in the range of 0.5mm2 to 2.5mm2.  
Insulation: XLPE to EN 50290. Suitable alternative materials are under consideration.  
Pair Identification: Black&Blue color with number on the cores for multi pairs, start with 1 in the centre.  
Wrapping: At least 1 layer of plastic tape.  
Collective Screen: Aluminimum foil tape over a tinned copper drain wire.  
Inner Sheath: Halogen free flame retardant compound LSZH, to EN 50290-2-27.  
Lead Sheath: Lead sheath comply with EN 50307.  
Bedding: Halogen free flame retardant compound LSZH, to EN 50290-2-27.  
Metallic Protection: Round galvanised steel wires armour.  
Outer Sheath: Halogen free flame retardant compound LSZH, to EN 50290-2-27.  

 

Electrical data at 20°C

 

 
Character
Unit     Values  
Conductor size nom. mm² 0.5 0.75   1.0 1.5
Conductor resistance max. Ω/km 36.7 25.0   18.5 12.3
Insulation resistance min. MΩ x km     5000  
L/R (ratio) max. µH/Ω   25     40
Inductance max. mH/km     1  
Mutual capacitance max. nF/m   65     75
Capacitance unbalance max. pF/500 m     500  
Test voltage   V     2000  
Operating voltage U0 / U max. V     500  

downloadpdf