Application
Suitable for connecting instruments and control systems for analogue or digital signal transmission.
Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial.
Construction
Conductor: | Solid, stranded or flexible plain or metal coated copper in accordance with class1, 2 or 5 of | |
HD383 in the range of 0.5mm2 to 2.5mm2. | ||
Insulation: | PE, PVC or XLPE to EN 50290. Suitable alternative materials are under consideration. | |
Pair Identification: | Black&Blue color with number on the cores for multi pairs, start with 1 in the centre. | |
Individual Screen: | Aluminimum foil tape over a tinned copper drain wire. | |
Wrapping: | At least 1 layer of plastic tape. | |
Collective Screen: | Aluminimum foil tape over a tinned copper drain wire. | |
Inner Sheath: | Polyvinyl chloride PVC, to EN 50290-2-22. | |
Metallic Protection: | Round galvanised steel wires armour. | |
Outer Sheath: | Polyvinyl chloride PVC, to EN 50290-2-22. |
Electrical data at 20°C
Character |
Unit | Values | |||||
Conductor size | nom. | mm² | 0.5 | 0.75 | 1.0 | 1.5 | |
Conductor resistance | max. | Ω/km | 36.7 | 25.0 | 18.5 | 12.3 | |
Insulation resistance | |||||||
PVC Insulation | min. | MΩ x km | 100 | ||||
PE/XLPE Insulaiton | min. | MΩ x km | 5000 | ||||
L/R (ratio) | max. | µH/Ω | 25 | 40 | |||
Inductance | max. | mH/km | 1 | ||||
Mutual capacitance | |||||||
PVC Insulation | max. | nF/m | 160 | 170 | |||
PE/XLPE Insulation | max. | nF/m | 100 | 100 | |||
Capacitance unbalance | max. | pF/500 m | 500 | ||||
Test voltage | V | 2000 | |||||
Operating voltage U0 / U | max. | V | 500 |