Application
Suitable for connecting instruments and control systems for analogue or digital signal transmission. Recommended for direct burial, especially in presence of oil and aggressive chemical substances
Construction

| Conductor: | Solid, stranded or flexible plain or metal coated copper in accordance with class1, 2 or 5 of | ||||||||||
| HD383 in the range of 0.5mm2 to 2.5mm2. | |||||||||||
| Insulation: | PVC or XLPE to EN 50290. Suitable alternative materials are under consideration. | ||||||||||
| Pair Identification: | Black&Blue color with number on the cores for multi pairs, start with 1 in the centre. | ||||||||||
| Wrapping: | At least 1 layer of plastic tape. | ||||||||||
| Collective Screen: | Aluminimum foil tape over a tinned copper drain wire. | ||||||||||
| Inner Sheath: | Polyvinyl chloride PVC, to EN 50290-2-22. | ||||||||||
| Lead Sheath: | Lead sheath comply with EN 50307. | ||||||||||
| Bedding: | Polyvinyl chloride PVC, to EN 50290-2-22. | ||||||||||
| Metallic Protection: | Round galvanised steel wires armour. | ||||||||||
| Outer Sheath: | Polyvinyl chloride PVC, to EN 50290-2-22. | ||||||||||
Electrical data at 20°C
Character |
Unit | Values | |||||
| Conductor size | nom. | mm² | 0.5 | 0.75 | 1.0 | 1.5 | |
| Conductor resistance | max. | Ω/km | 36.7 | 25.0 | 18.5 | 12.3 | |
| Insulation resistance | |||||||
| PVC Insulation | min. | MΩ x km | 100 | ||||
| XLPE Insulaiton | min. | MΩ x km | 5000 | ||||
| L/R (ratio) | max. | µH/Ω | 25 | 40 | |||
| Inductance | max. | mH/km | 1 | ||||
| Mutual capacitance | |||||||
| PVC Insulation | max. | nF/m | 120 | 130 | |||
| XLPE Insulation | max. | nF/m | 65 | 75 | |||
| Capacitance unbalance | max. | pF/500 m | 500 | ||||
| Test voltage | V | 2000 | |||||
| Operating voltage U0 / U | max. | V | 500 | ||||