XLPE Insulated, PVC Bedded, Alminium Wire Armoured, PVC Sheathed Cable

Application

These power cable for fixed installations such as distribution networks or industrial installations.

Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.

Armoured cable suitable for direct burial.

12

Construction

1 Conductor: Plain annealed copper, class1 solid or class 2 stranded acc. to IEC 60228.

Flexible class 5 or tinned conductor could be offer upon request.

2 Insulation: Cross-linked polyethlene (XLPE) compound as per IEC 60502-1.

Insulation Color Code:

Number of Cores Color Code to IEC 60502-1 Color Code to BS 5467
1 Red or Black Brown or Blue

3 Bedding: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1.

Bedding Colour: Black or other color as per customer request.

4 Armour: Aluminium wire armoured (AWA).

5 Outer Sheath: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1.

Outer Sheath Color: Black or other color as per customer request.

Electrical Characteristics

Recommended rated voltages U0

Highest system voltage     Rated voltage (U0) (kV)
(Um) (kV)   Categories A and B   Category C
1,2   0,6   0,6
Routine test voltages        
         
Rated voltage U0 (kV)       0,6
Test voltage (kV)       3,5
Maximum conductor temperatures for different types of insulating compound
   
Maximum conductor temperature (°C)  
Normal operation   Short-circuit (5 s maximum duration)
90         250

Operating Temperature: -15°C to 90°C

Test Voltage: 3.5 kV for 5 minutes

Installation Reference

Min.Bending Radius (mm): 8 x cable overall diameter

Max.Pulling Tension (N/mm2): 50

Reference Standards

Design Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1