Application
These power cable for fixed installations such as distribution networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.
Construction
1 Conductor: Plain annealed copper, class1 solid or class 2 stranded circular, compacted or sectored.
2 | Insulation: Cross-linked polyethlene (XLPE) compound as per IEC 60502-1. | |||
Insulation Colour: | ||||
Number of Cores | Color Code to IEC 60502-1 | Color Code to BS 5467 | ||
4 | Red, Yellow, Blue and Black | Blue, Brown, Black and Grey | ||
Assembly: Cores cabled together with PP filler and covered with non-woven tape. | ||||
3 | Bedding: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1. | |||
Bedding Colour: Black or other color as per customer request. | ||||
4 | Screen: Copper tape. | |||
5 | Outer Sheath: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1. | |||
Outer Sheath Colour: Black or other color as per customer request. |
Electrical Characteristics
Recommended rated voltages U0
Highest system voltage | Rated voltage (U0) (kV) | ||||
(Um) (kV) | Categories A and B | Category C | |||
1,2 | 0,6 | 0,6 | |||
Routine test voltages | |||||
Rated voltage U0 (kV) | 0,6 | ||||
Test voltage (kV) | 3,5 | ||||
Maximum conductor temperatures for different types of insulating compound | |||||
Maximum conductor temperature (°C) | |||||
Normal operation | Short-circuit (5 s maximum duration) | ||||
90 | 250 |
Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes
Reference Standards
Design Specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1
Installation Reference
Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 50