Application
These cables are suitable for indoor and outdoor applications, where a high safety against flame is required .
Public address and emergency voice communication system and traffic control centres.
Control and instrumentation service in industrial, commercial and residential buildings.
Such as: Schools&Universities, Hospital, Markets & Malls, Hotels, Theatres, Cinemas, Airports, Underground stations, Tunnels, Recreational places& Amusement parks, Indoor work places.
Construction
1 | Conductor: Plain annealed copper, class1 solid or class 2 stranded as per IEC 60228. | |||||
Flexible class 5 or tinned conductor could be offer upon request. | ||||||
2 | Fire Barrier: Mica tape (MGT). | |||||
3 | Insulation: Cross-linked polyethlene (XLPE) compound as per IEC 60502-1. | |||||
Insulation Colour: | ||||||
Number of Cores | Color Code to IEC 60502-1 | Color Code to BS 5467 | ||||
2 | Red & Black | Brown & Blue | ||||
3 | Red, Yellow and Blue | Brown, Black and Grey | ||||
4 | Red, Yellow, Blue and Black | Blue, Brown, Black and Grey | ||||
5 | Red, Yellow, Blue, Black and | Green / Yellow, Blue, Brown, | ||||
Green / Yellow | Black and Grey | |||||
Assembly: Cores cabled together with PP filler and covered with non-woven tape. | ||||||
4 | Outer Sheath: Low smoke zero halogen (LSZH) compound ST8 (90°C) of IEC 60502-1. | |||||
Outer Sheath Colour: Black or other color as per customer request. |
Electrical Characteristics
Recommended rated voltages U0 | |||||
Highest system voltage | Rated voltage (U0) (kV) | ||||
(Um) (kV) | Categories A and B | Category C | |||
1,2 | 0,6 | 0,6 | |||
Routine test voltages | |||||
Rated voltage U0 (kV) | 0,6 | ||||
Test voltage (kV) | 3,5 | ||||
Maximum conductor temperatures for different types of insulating compound | |||||
Maximum conductor temperature (°C) | |||||
Normal operation | Short-circuit (5 s maximum duration) | ||||
90 | 250 | ||||
Operating Temperature: -15°C to 90°C | |||||
Test Voltage: 3.5 kV for 5 minutes |
Installation Reference
Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 50