CU/MGT/XLPE/LSZH (2 Cores - 5 Cores) Mica Tape, XLPE Insulated, LSZH Sheathed Cable

Application

These cables are suitable for indoor and outdoor applications, where a high safety against flame is required .

Public address and emergency voice communication system and traffic control centres.

Control and instrumentation service in industrial, commercial and residential buildings.

Such as: Schools&Universities, Hospital, Markets & Malls, Hotels, Theatres, Cinemas, Airports, Underground stations, Tunnels, Recreational places& Amusement parks, Indoor work places.

34

Construction

1 Conductor: Plain annealed copper, class1 solid or class 2 stranded as per IEC 60228.  
    Flexible class 5 or tinned conductor could be offer upon request.  
2 Fire Barrier: Mica tape (MGT).      
3 Insulation: Cross-linked polyethlene (XLPE) compound as per IEC 60502-1.  
  Insulation Colour:        
             
    Number of Cores Color Code to IEC 60502-1 Color Code to BS 5467    
    2 Red & Black Brown & Blue    
    3 Red, Yellow and Blue Brown, Black and Grey    
    4 Red, Yellow, Blue and Black Blue, Brown, Black and Grey    
    5 Red, Yellow, Blue, Black and Green / Yellow, Blue, Brown,    
    Green / Yellow Black and Grey    
         
  Assembly: Cores cabled together with PP filler and covered with non-woven tape.  
4 Outer Sheath: Low smoke zero halogen (LSZH) compound ST8 (90°C) of IEC 60502-1.  
  Outer Sheath Colour: Black or other color as per customer request.  

Electrical Characteristics

Recommended rated voltages U0  
Highest system voltage     Rated voltage (U0) (kV)
(Um) (kV)   Categories A and B   Category C
1,2   0,6   0,6
Routine test voltages        
         
Rated voltage U0 (kV)       0,6
Test voltage (kV)       3,5
Maximum conductor temperatures for different types of insulating compound
     
Maximum conductor temperature (°C)  
Normal operation   Short-circuit (5 s maximum duration)
90         250
Operating Temperature: -15°C to 90°C  
Test Voltage: 3.5 kV for 5 minutes  

Installation Reference

Min.Bending Radius (mm): 8 x cable overall diameter

Max.Pulling Tension (N/mm2): 50

downloadpdf