600/1000V LSZH Sheathed, Overall screened & Armoured (single core)

600 1000V LSZH Sheathed Armoured single core 2

Application:

This range of screened cables drastically reduce interferences from electrical noise, especially in Variable Speed Drive (VSD) applications and are manufactured with fixed conductors.

Standard: Basic design to IEC 60502-1

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

VOLTAGE RATING
600/1000V

CABLE CONSTRUCTION 
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Inner sheath(optional): LSZH Compound
Armouring(optional): Aluminium Wire
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)

COLOUR CODE
Insulation colour as per bs7671

  with earth conductor without earth conductor
2Cores - Brown,Blue
3Cores Yellow/Green,Brown,Blue Brown,Gray,Black
4Cores Yellow/Green,Brown,Gray,Black Brown,Gray,Black,Blue
5Cores Yellow/Green,Brown,Gray,Black,Blue Brown,Gray,Black,Blue,Black
above 5 Cores Yellow/Green,Black Numbered Black Numbered

sheath colour: Black

Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C
250°C in short-circuit for 5s max.
Minimum bending radius: 8 x Overall Diameter (unarmoured cable)
10 x Overall Diameter (armoured cable)

CONSTRUCTION PARAMETERS

Conductor FTX300 1RZ1MZ1-R
No. of Core X Cross Section No./ Nominal Diameter Of Strands Nominal Insulation Thickness            
Nominal Sheath Thickness Diameter Under Screen Diameter Over Inner Sheath Armour Wire Diameter Nominal Overall Diameter Approx. Weight
Noxmm2 No./mm mm mm kg/km mm mm mm kg/km
1x70 19/2.14 1.1 1.8 15.2 17.6 20.1 23.9 1400
1x95 19/2.52 1.1 1.8 17.1 19.5 22.0 25.8 1700
1x120 37/2.03 1.2 1.8 19.0 20.8 24.0 27.8 2000
1x150 37/2.25 1.4 1.8 21.0 22.8 26.0 29.8 2400
1x185 37/2.52 1.6 1.8 23.2 25.0 28.2 32.0 2800
1x240 61/2.25 1.7 1.9 26.1 27.9 31.1 35.1 3500
1x300 61/2.52 1.8 2.0 28.7 30.5 33.7 37.9 4200
1x400 61/2.85 2.0 2.1 32.5 34.3 38.3 42.7 5400
1x500 61/3.20 2.2 2.2 36.0 37.8 41.8 46.4 6500
1x630 127/2.52 2.4 2.3 40.4 42.2 46.2 51.0 8200
1x800 127/2.85 2.6 2.5 45.5 47.3 52.3 57.5 10400
1x1000 127/3.20 2.8 2.7 50.4 52.2 57.2 62.4 13000

Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)

Conductor crosssectional area Reference Method 4 (enclosed in conduit in thermally insulating wall etc) Reference Method 3 (enclosed in conduit on a wall or in trunking etc) Reference Method 12 (free air) In single-way ducts Laid direct in ground
2 cables, single- phase a.c. or d.c. 3 or 4 cables,  3-phase a.c. 2 cables, single- phase a.c. or d.c 3 or 4 cables,  3-phase a.c. 3 cables 3-phase a.c. trefoil touching 2 cables, singlephase a.c. or d.c. 3 or 4 cables, 3-phase a.c. 2 cables, singlephase a.c. or d.c. 3 or 4 cables, 3-phase a.c.
1 2 3 4 5 6 7 8 9 10
mm2 A A A A AA A A AA A
70 303 277 322 293 285 310 280 340 290
95 367 333 389 352 346 365 330 405 345
120 425 383 449 405 402 410 370 460 389
150 488 437 516 462 463 445 405 510 435
185 557 496 587 524 529 485 440 580 490
240 656 579 689 612 625 550 500 670 560
300 755 662 792 700 720 610 550 750 630
400 853 717 899 767 815 640 580 830 700
500 962 791 1016 851 918 690 620 910 770
630 1082 861 1146 935 1027 750 670 1000 840
800 1170 904 1246 987 1119 828 735 1117 931
1000 1261 961 1345 1055 1214 919 811 1254 1038

Voltage Drop (Per Amp Per Meter)

Conductor crosssectional area 2 cables d.c. 2 cables singlephase a.c. 3 or 4 cables three-phase a.c. 2 cables singlephase a.c. 3 or 4 cables, 3-phase a.c. touching
Reference Method 1 & 11 (touching) Reference Method 1, 11 & 12 (in trefoil touching) Reference Method 1 & 11 (Flat touching) In ducts In ground In ducts In ground
1 2 3 4 5 6 7 8 9
mm² mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
    r x z r x z r x z        
70 0.67 0.68 0.20 0.71 0.59 0.17 0.62 0.6 0.25 0.65 0.80 0.70 0.70 0.61
95 0.49 0.51 0.195 0.55 0.44 0.17 0.47 0.46 0.24 0.52 0.65 0.53 0.56 0.46
120 0.36 0.41 0.190 0.45 0.35 0.165 0.39 0.38 0.24 0.44 0.55 0.43 0.48 0.37
150 0.31 0.33 0.185 0.38 0.29 0.160 0.33 0.31 0.23 0.39 0.50 0.37 0.43 0.32
185 0.25 0.27 0.185 0.33 0.23 0.160 0.28 0.26 0.23 0.34 0.45 0.31 0.39 0.27
240 0.195 0.21 0.180 0.28 0.18 0.155 0.24 0.21 0.22 0.30 0.40 0.26 0.35 0.23
300 0.155 0.17 0.175 0.25 0.145 0.150 0.21 0.17 0.22 0.28 0.37 0.24 0.32 0.21
400 0.115 0.145 0.170 0.22 0.125 0.150 0.195 0.160 0.21 0.27 0.35 0.21 0.30 0.19
500 0.093 0.125 0.170 0.21 0.105 0.145 0.180 0.145 0.20 0.25 0.33 0.20 0.28 0.18
630 0.073 0.105 0.165 0.195 0.092 0.145 0.170 0.135 0.195 0.24 0.30 0.19 0.26 0.17
800 0.056 0.090 0.160 0.190 0.086 0.140 0.165 0.130 0.180 0.23 0.28 0.18 0.24 0.16
1000 0.045 0.092 0.155 0.180 0.080 0.135 0.155 0.125 0.170 0.21 0.26 0.17 0.22 0.15