Flame Retardant CAT5e CWB/SWB/SWA Armoured Data Cables

CAT5e U/UTP4P24 CWB/SWB/SWA
CAT5e F/UTP4P24 CWB/SWB/SWA
CAT5e SF/FTP4P24 CWB/SWB/SWA

Flame Retardant CAT5e CWBSWBSWA Armoured Data Cables

Application:

Cat5E is a cable standard for Gigabit Ethernet and other network protocol, suitable for basic voice and data installations up to 100 MHz. In addition, these cables can be offered with copper wire braid armoured & flame retardant outer sheath, providing additional mechanically protection still maintaining the flexibility of the cable.

STANDARDS: Basic design adapted to EN50173

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)** EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)** EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING

60V

CABLE CONSTRUCTION

Conductors: 24AWG solid bare copper.

Insulation: HDPE.

Twinning: Two coloured insulated conductors twisted together to form a pair.

Inner Sheath: Flame retardant, low smoke and halogen-free polyolefin, coloured black

Armouring: cwb: copper Wire Braid

swb: Steel Wire

Braid swa: Steel Wire

Armour Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

Cat5E F/UTP: These cables have collective shielding of aluminium/Polyester tape with drain wire.

Cat5E SF/UTP: These cables have double collective shieldings of aluminium/Polyester tape & copper wire braid.

Physical AND THERMAL PROPERTIES

Temperature range: -30°C ~ +75°C

Minimum bending radius during installation (mobile state): 8 x Overall Diameter

Minimum bending radius during operation (fixed state): 4 x Overall Diameter

Electrical Properties

AWG   24
Nominal Conductor Diameter mm 0.5/0.53
Maximum DC Resistant@20°C Ω/100m 9.38
Maximum DCR Unbalance % 5
Maximum Mutual Capacitance pF/m 55.8
Maximum Capacitance Unbalance pF/100m 330
Characteristic Impedance@1-100MHz Ω 100+/-15
Maximum Propagation Delay Skew ns/100m 45

Transmission Properties

FREQ MHz Maximum Attenuation dB/100m Minimum NEXT dB Minimum PSNEXT dB Minimum ELFEXT dB/100m Minimum PSELFEXT dB/100m Minimum RL dB
0.772 1.8 67.0 64.0 66.0 63.0
1 2.0 65.3 62.3 63.8 60.8 20.0
4 4.1 56.3 53.3 51.7 48.7 23.0
8 5.8 51.8 48.8 45.7 42.7 24.5
10 6.5 50.3 47.3 43.8 40.8 25.0
16 8.2 47.3 44.3 39.7 36.7 25.0
20 9.3 45.8 42.8 37.7 34.7 25.0
25 10.4 44.3 41.3 35.8 32.8 24.3
31.25 11.7 42.9 39.9 33.9 30.9 23.6
62.5 17.0 38.4 35.4 27.8 24.8 21.5
100 22.0 35.3 32.3 23.8 20.8 20.1

Cat5E SF/UTP

CONSTRUCTION PARAMETERS

Cable Code Construction No. of elements×No. of cores in element×Conductor diameter Nominal Insulation Thickness Nominal Inner Sheath Thickness Nominal Outer Sheath Thickness Nominal Overall Diameter Nominal Weight
  mm mm mm mm mm kg/km
CAT5E U/UTP CWB 4×2×0.5 0.2 0.6 1.0 7.68 97
CAT5E U/UTP SWB 4×2×0.5 0.2 0.6 1.0 7.68 93
CAT5E U/UTP SWA 4×2×0.5 0.2 0.6 1.0 8.68 165
CAT5E F/UTP CWB 4×2×0.53 0.2 0.6 1.0 8.28 116
CAT5E F/UTP SWB 4×2×0.53 0.2 0.6 1.0 8.28 112
CAT5E F/UTP SWA 4×2×0.53 0.2 0.6 1.0 9.28 192
CAT5E SF/UTP CWB 4×2×0.53 0.2 0.6 1.0 8.76 123
CAT5E SF/UTP SWB 4×2×0.53 0.2 0.6 1.0 8.76 119
CAT5E SF/UTP SWA 4×2×0.53 0.2 0.6 1.0 9.76 216