150 Ω Profibus L2 Outdoor + Industry BUS CABLE

Profibus L2 Outdoor Industry

Application:

This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the information exchange between different automation systems as well as for communication with the connected decentralized field units, serial field bus systems are used. The types mentioned here are suitable for outdoor laying (PE jacket) and industry laying (PUR jacket).

Construction:

Type/Area of Application Fixed Installation, Outdoor /Heavy Duty
Cable Construction 1x2x0.64 mm
Inner Conductor Diameter Copper, bare (AWG 22/1)
Conductor Insulation Foam-skin-PE
Conductor Colors Red, green
Stranding Element 2 conductors + 2 fillers stranded together
Shielding 1 Polyester foil over stranded bundle
Shielding 2 Polyester foil, aluminum-lined
Total Shielding Cu braid, tinned
Outer Jacket Material PE/PUR
Outer Diameter 8.0 mm ± 0.4 mm
Outer Jacket Color Black

Electrical Data:

CharacteristicImpedance@3-20MHz 150 Ω ± 10 Ω
Conductor Resistance 55.0 Ohm/km max.
Insulation Resistance 1.00 GOhm x km min.
Mutual Capacitance@1 KHz 30.0 nF/km nom.
Working Voltage  Max: 250 V
Test Voltage 1.5 KV
Attenuation 9.6kHz 2.5dB/km
38.4kHz 4.0dB/km
4.0MHz 22.0dB/km
16.0MHz 42.0dB/km

Technical Data:

Weight approximately 66.0 kg/km
Min. Bending Radius (Laying) 15 x OD mm
Operating Temp.Range, min. -40 °C
Operating Temp.Range, max. +70 °C