P34 BFOU-HCF 0.6/1 kV Fire resistant NEK606 cable

P34 BFOU HCF 0.61 kV

Applications : These cables are fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100℃ hydrocarbon fire.
Standards : IEC 60092-353; IEC 60092-351; IEC 60092-359; IEC 60331-21; IEC 60332-1; IEC 60332-3-22; IEC 60754-1,2; IEC 61034-1,2; NEK 606:2004
Conductors : Tinned annealed stranded compacted copper to IEC 60228 class 2.
Insulation : Mica tape + Halogen free EPR/XLPE.
Bedding : Halogen free compound.
Armour : Tinned copper wire braid.
Outer Sheath1 : HC-fire protection : Extruded thermoplastic fire protection compound.
Taping : Lapped glass fibre tape.
Outer Sheath2 : Flame retardant halogen-free thermoplastic compound, SHF1, coloured black.

Electrical Characteristics :

Nominal Cross Section Area

mm²

1.5

2.5

4

6

16

35

Nominal Conductor Diameter

mm

1.6

2.1

2.6

3.2

5.1

7.4

Maximum DC Resistant@20℃

Ω/km

12.2

7.56

4.7

3.11

1.16

0.529

Continuous Current Rating@45℃1 Core

A

23

30

40

52

96

157

Continuous Current Rating@45℃2 Core

A

20

26

34

44

82

133

Continuous Current Rating@45℃3&4 Core

A

16

21

28

36

67

110

Short Circuit Current 1s

A

210

360

570

860

2290

5010

Operating Voltage

KV

0.6/1

0.6/1

0.6/1

0.6/1

0.6/1

0.6/1

Nominal Cross Section Area

mm²

50

70

95

120

150

185

240

300

Nominal Conductor Diameter

mm

8.7

10.3

12.2

13.8

15.1

17.0

19.6

21.9

Maximum DC Resistant@20℃

Ω/km

0.391

0.27

0.195

0.154

0.126

0.1

0.0762

0.0607

Continuous Current Rating@45℃1 Core

A

196

242

293

339

389

444

522

601

Continuous Current Rating@45℃2 Core

A

167

206

249

288

331

444

444

511

Continuous Current Rating@45℃3&4 Core

A

137

169

205

237

272

311

365

421

Short Circuit Current 1s

A

7150

10020

13590

17170

21460

26470

34340

42930

Operating Voltage

KV

0.6/1

0.6/1

0.6/1

0.6/1

0.6/1

0.6/1

0.6/1

0.6/1

Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN=I1/ ³√ N ), I1= Current rating for 1-core, N = Number of cores.

Ambient Temperature Correction Factors :

Ambient Temperature Correction Factors

35

40

45

50

55

60

65

70

75

80

Rating Factor

1.1

1.05

1.0

0.94

0.88

0.82

0.74

0.67

0.58

0.47

Mechanical and Thermal Properties :

Bending Radius :20×OD (during installation); 12×OD (fixed installed).

Temperature Range : -20℃ ~ +90℃.

Dimensions and Weight :

Construction No. of cores×Cross section

(mm²)

Nominal Insulation Thickness

mm

Nominal Diameter Over Bedding

mm

Nominal Diameter Over Sheath1

mm

Nominal Overall Diameter

mm

Nominal Weight

kg/km

1×50

1.4

15.0

18.5

45.5

2900

1×70

1.4

16.5

20.5

47.5

3300

1×95

1.6

18.5

23.0

50.5

3800

1×120

1.6

20.5

25.0

52.5

4260

1×150

1.8

23.0

27.0

54.5

4750

1×185

2.0

25.0

29.5

57.5

5380

1×240

2.2

28.0

32.5

66.0

7050

1×300

2.4

30.5

35.5

68.0

8000

2×1.5

1.0

10.0

13.0

40.5

1890

2×2.5

1.0

11.0

14.5

42.0

2080

3×1.5

1.0

10.5

14.0

42.0

2140

3×2.5

1.0

11.5

15.0

42.5

2200

3×4

1.0

13.0

16.5

43.0

2400

3×6

1.0

14.0

18.0

45.0

2600

3×16

1.0

18.5

23.0

50.0

3500

3×35

1.2

25.0

29.5

57.5

4840

3×70

1.4

33.0

39.0

72.0

8150

3×120

1.6

41.0

48.0

81.5

11300

3×150

1.8

46.0

54.5

88.5

13300

4×2.5

1.0

12.5

16.5

44.0

2300

4×6

1.0

15.5

19.5

47.5

2870

4×16

1.0

20.5

25.0

53.5

3830

7×1.5

1.0

14.0

17.5

44.5

2550

12×1.5

1.0

18.5

22.5

50.0

3140

27×1.5

1.0

26.5

31.0

64.5

5070

7×2.5

1.0

15.0

19.0

46.0

2760

12×2.5

1.0

20.5

24.5

52.0

3500