PE Insulated, LSZH Sheathed, CWB Screened Instrumentation Cables (Single Pair)

RE-2Y(C)H 90°C / 300V

PE Insulated LSZH Sheathed CWB Screened Instrumentation Cables Single Pair

STANDARDS Basic design to EN 50288-7
APPLICATION Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations.

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Sunlight Resistance

UL 1581 section 1200

Oil Resistance

ICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING 300V
CABLE CONSTRUCTION  
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: PE compound, EN 50290. 2-23.
Pair: Two conductors twisted to form a pair
Lay-up: Pairs laid up in layers of optimum pitch
Separator: Polyester tape
Overall Screen: Tinned copper wire braid
Outer sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE  
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems
Physical AND THERMAL PROPERTIES  
Temperature Range During Operation (Fixed State): -30°C – +70°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 7.5 X Overall Diameter

CONSTRUCTION PARAMETERS

 Cable Code

RE-2Y(C)H

No. of Pairs

x2xCross Section

Copper

Weight

Approx.

Weight

 

No.x2xmm2

Kg/km

Kg/km

RE-2Y(C)H 1P0.5

1x2x0.50

8.3

110

RE-2Y(C)H 1P0.75

1x2x0.75

8.7

119

RE-2Y(C)H 1P1.0

1x2x1.0

9.4

135

RE-2Y(C)H 1P1.3

1x2x1.3

9.7

140

Note : Other conductor sizes & core configurations are available upon request

Electrical PROPERTIES

Conductor Area Size

mm 2

0.5

0.75

1.0

1.3

1.5

Insulation thickness (nominal)

mm

0.4

0.4

0.4

0.45

0.45

Conductor resistance (20°C)

Ω/km

36.7

25

18.5

14.2

12.3

Insulation resistance (20°C)

MΩ.km(Min.)

5000

Mutual Capacitance (1 kHz)

pF/m(Max.)

115

Capacitance unbalance(1 kHz)

pF/500 m (Max.)

300

L / R (ratio) (max.)

μH/Ω

25

25

25

40

40

Operating voltage Urms

V

300

Test Voltage

Core to Core

V

1500

Core to Screen

V

1500