PE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Multipair)

RE-2Y(St)HSWAH 90°C / 300V

PE Insulated LSZH Sheathed Overall Screened Armoured Instrumentation Cables Multipair

STANDARDS  Basic design to EN 50288-7
APPLICATION   Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations.

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);  

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation   (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;  

CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;  

CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;  

CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Sunlight Resistance

UL 1581 section 1200

Oil Resistance

ICEA S-73-532**

Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of tensite strength/min.60% of elongation.

VOLTAGE RATING 300V
CABLE CONSTRUCTION   
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2. 
Insulation: PE compound, EN 50290. 2-23. 
Pair: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Binder tape: PETP transparent tape
Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²
Inner Sheath: LSZH(Low Smoke Zero Halogen) sheath
Amouring:  Galvanized steel wire armour
Outer Sheath:  Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4  as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE  
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems
Physical AND THERMAL PROPERTIES  
Temperature Range During Operation (Fixed State): -30°C – +90°C
Temperature Range During Installation (Mobile State): -20°C – +50°C
Minimum Bending Radius: 10 X Overall Diameter 

CONSTRUCTION PARAMETERS

 Cable Code

RE-2Y(St)HSWAH

No. of  

Pairsx2 

xCross  

Section

Nominal 

Insulation 

Thick 

-ness

Nominal 

Inner Sheath 

Thick 

-ness

Nominal 

Overall  

Diameter  

Over 

Inner   

Sheath

Nominal 

 Armour  

Wire  

Diameter

Nominal 

Outer 

Sheath 

Thick 

-ness

Nominal 

Overall 

Diameter

Approx.  

Weight

 

No.x2xmm2

mm2 

mm 

mm 

mm 

mm

mm 

kg/km 

0.5mm2, Multipair

RE-2Y(St)HSWAH 2P0.5

2x2x0.5

0.35

0.9

7.6

0.9

1.3

12.0

262

RE-2Y(St)HSWAH 4P0.5

3x2x0.5

0.35

0.9

8.8

0.9

1.4

13.4

325

RE-2Y(St)HSWAH 5P0.5

4x2x0.5

0.35

1.0

9.8

0.9

1.4

14.4

375

RE-2Y(St)HSWAH 6P0.5

5x2x0.5

0.35

1.0

10.6

0.9

1.4

15.2

411

RE-2Y(St)HSWAH 8P0.5

8x2x0.5

0.35

1.0

11.3

0.9

1.4

15.9

473

RE-2Y(St)HSWAH 10P0.5

10x2x0.5

0.35

1.1

12.9

0.9

1.5

17.7

537

RE-2Y(St)HSWAH 12P0.5

12x2x0.5

0.35

1.1

13.5

0.9

1.5

18.3

576

RE-2Y(St)HSWAH 16P0.5

16x2x0.5

0.35

1.1

15.2

0.9

1.5

20.0

824

RE-2Y(St)HSWAH 20P0.5

20x2x0.5

0.35

1.2

16.9

0.9

1.6

21.9

949

RE-2Y(St)HSWAH 24P0.5

24x2x0.5

0.35

1.2

18.3

1.25

1.6

24.0

1030

0.75mm2, Multipair

RE-2Y(St)HSWAH 2P0.75

2x2x0.75

0.38

0.9

8.5

0.9

1.4

13.1

308

RE-2Y(St)HSWAH 4P0.75

3x2x0.75

0.38

1.0

10.0

0.9

1.4

14.6

383

RE-2Y(St)HSWAH 5P0.75

4x2x0.75

0.38

1.0

10.9

0.9

1.4

15.5

448

RE-2Y(St)HSWAH 6P0.75

5x2x0.75

0.38

1.0

11.8

0.9

1.4

16.4

482

RE-2Y(St)HSWAH 8P0.75

8x2x0.75

0.38

1.1

12.8

0.9

1.5

17.6

534

RE-2Y(St)HSWAH 10P0.75

10x2x0.75

0.38

1.1

14.5

0.9

1.5

19.3

654

RE-2Y(St)HSWAH 12P0.75

12x2x0.75

0.38

1.1

15.1

0.9

1.5

19.9

826

RE-2Y(St)HSWAH 16P0.75

16x2x0.75

0.38

1.2

17.3

0.9

1.6

22.3

967

RE-2Y(St)HSWAH 20P0.75

20x2x0.75

0.38

1.3

19.2

1.25

1.6

24.9

1118

RE-2Y(St)HSWAH 24P0.75

24x2x0.75

0.38

1.3

20.8

1.25

1.6

26.7

1294

1.0mm2, Multipair

RE-2Y(St)HSWAH 2P1.0

2x2x1.0

0.4

0.9

9.2

0.9

1.4

13.8

357

RE-2Y(St)HSWAH 4P1.0

3x2x1.0

0.4

1.0

10.9

0.9

1.4

15.5

450

RE-2Y(St)HSWAH 5P1.0

4x2x1.0

0.4

1.0

11.9

0.9

1.4

16.5

509

RE-2Y(St)HSWAH 6P1.0

5x2x1.0

0.4

1.0

13.0

0.9

1.4

17.6

565

RE-2Y(St)HSWAH 8P1.0

8x2x1.0

0.4

1.1

14.0

0.9

1.5

18.8

651

RE-2Y(St)HSWAH 10P1.0

10x2x1.0

0.4

1.1

15.9

0.9

1.5

20.7

886

RE-2Y(St)HSWAH 12P1.0

12x2x1.0

0.4

1.2

16.8

0.9

1.5

21.6

946

RE-2Y(St)HSWAH 16P1.0

16x2x1.0

0.4

1.2

19.0

1.25

1.6

24.7

1173

RE-2Y(St)HSWAH 20P1.0

20x2x1.0

0.4

1.3

21.1

1.25

1.7

27.0

1318

RE-2Y(St)HSWAH 24P1.0

24x2x1.0

0.4

1.4

23.1

1.25

1.7

29.0

1488

1.3mm2, Multipair

RE-2Y(St)HSWAH 2P1.3

2x2x1.3

0.45

1.0

10.4

0.9

1.4

15.0

405

RE-2Y(St)HSWAH 4P1.3

3x2x1.3

0.45

1.0

12.0

0.9

1.4

16.6

511

RE-2Y(St)HSWAH 5P1.3

4x2x1.3

0.45

1.1

13.4

0.9

1.5

18.2

595

RE-2Y(St)HSWAH 6P1.3

5x2x1.3

0.45

1.1

14.6

0.9

1.5

19.4

673

RE-2Y(St)HSWAH 8P1.3

8x2x1.3

0.45

1.2

15.7

0.9

1.5

20.5

870

RE-2Y(St)HSWAH 10P1.3

10x2x1.3

0.45

1.2

17.9

0.9

1.6

23.6

1012

RE-2Y(St)HSWAH 12P1.3

12x2x1.3

0.45

1.3

18.9

1.25

1.6

24.6

1143

RE-2Y(St)HSWAH 16P1.3

16x2x1.3

0.45

1.3

21.4

1.25

1.7

27.3

1407

RE-2Y(St)HSWAH 20P1.3

20x2x1.3

0.45

1.4

23.8

1.25

1.8

29.9

1601

RE-2Y(St)HSWAH 24P1.3

24x2x1.3

0.45

1.5

25.9

1.25

1.8

32.0

2048

1.5mm2, Multipair

RE-2Y(St)HSWAH 2P1.5

2x2x1.5

0.45

1.0

10.8

0.9

1.4

15.4

448

RE-2Y(St)HSWAH 4P1.5

3x2x1.5

0.45

1.1

12.7

0.9

1.5

17.5

530

RE-2Y(St)HSWAH 5P1.5

4x2x1.5

0.45

1.1

14.0

0.9

1.5

18.8

628

RE-2Y(St)HSWAH 6P1.5

5x2x1.5

0.45

1.2

15.2

0.9

1.5

20.0

835

RE-2Y(St)HSWAH 8P1.5

8x2x1.5

0.45

1.2

16.4

0.9

1.6

21.4

944

RE-2Y(St)HSWAH 10P1.5

10x2x1.5

0.45

1.3

18.8

1.25

1.6

24.5

1097

RE-2Y(St)HSWAH 12P1.5

12x2x1.5

0.45

1.3

19.7

1.25

1.7

25.6

1230

RE-2Y(St)HSWAH 16P1.5

16x2x1.5

0.45

1.4

22.5

1.25

1.7

28.4

1471

RE-2Y(St)HSWAH 20P1.5

20x2x1.5

0.45

1.5

25.0

1.25

1.8

31.1

1971

RE-2Y(St)HSWAH 24P1.5

24x2x1.5

0.45

1.5

27.1

1.25

1.8

33.2

2251

Note : Other conductor sizes & core configurations are available upon request

Electrical PROPERTIES

Conductor Area Size 

 mm 2  

0.5 

0.75  

1.0  

1.3

1.5  

Insulation thickness (nominal)

mm

0.35

0.38

0.4

0.45

0.45

Conductor resistance (20°C) 

 Ω/km 

36.7

25

18.5

14.2

12.3

Insulation resistance (20°C)

MΩ.km(Min.)

5000

Mutual Capacitance (1 kHz) 

pF/m(Max.)

 

 

up to 4 pairs

90 

90

90

102

102

 

above 4 pairs

75

75

75

85

85

Capacitance unbalance(1 kHz) 

pF/500 m (Max.)

500 

Inductance

mH/km (Max.)

1

L / R (ratio) (max.)

μH/Ω

25

25

25

40

40

Operating voltage Urms

V

300

Test Voltage 

Core to Core 

1500 

Core to Screen 

1500