XLPE Insulated, LSZH Sheathed & Overall Screened, Armoured Instrumentation Cables (Multipair)

RE-2X(St)HSWAH 90°C / 300V

XLPE Insulated LSZH Sheathed Overall Screened Armoured Instrumentation Cables Multipair

STANDARDS Basic design to EN 50288-7
APPLICATION Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations.
The armoured LSZH sheathed cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the LSZH sheath can reduce toxic smoke and fume emission.

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Sunlight Resistance

UL 1581 section 1200

Oil Resistance

ICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING 300V
CABLE CONSTRUCTION  
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Binder tape: PETP transparent tape
Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²
Inner Sheath: LSZH compound
Amouring: Galvanized steel wire armour
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE  
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems
Physical AND THERMAL PROPERTIES  
Temperature Range During Operation (Fixed State): -30°C – +90°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 10 X Overall Diameter

CONSTRUCTION PARAMETERS

Cable Code

RE-2X(St)HSWAH

No. of Pairs

x2xCross Section

Nominal

Insulation

Thick

-ness

Nominal

Inner Sheath

Thick

-ness

Nominal Overall

Diameter

Over

Inner

Sheath

Nominal

Armour

Wire

Diameter

Nominal

Outer

Sheath

Thick

-ness

Nominal Overall Diameter

Approx.

Weight

 

No.x2xmm2

mm2

mm

mm

mm

mm

mm

kg/km

0.5mm2, Multipair

RE-2X(St)HSWAH 2P0.5

2x2x0.5

0.35

0.9

7.6

0.9

1.3

12.0

269

RE-2X(St)HSWAH 4P0.5

3x2x0.5

0.35

0.9

8.8

0.9

1.4

13.4

325

RE-2X(St)HSWAH 5P0.5

4x2x0.5

0.35

1.0

9.8

0.9

1.4

14.4

375

RE-2X(St)HSWAH 6P0.5

5x2x0.5

0.35

1.0

10.6

0.9

1.4

15.2

423

RE-2X(St)HSWAH 8P0.5

8x2x0.5

0.35

1.0

11.3

0.9

1.4

15.9

473

RE-2X(St)HSWAH 10P0.5

10x2x0.5

0.35

1.1

12.9

0.9

1.5

17.7

521

RE-2X(St)HSWAH 12P0.5

12x2x0.5

0.35

1.1

13.5

0.9

1.5

18.3

592

RE-2X(St)HSWAH 16P0.5

16x2x0.5

0.35

1.1

15.2

0.9

1.5

20.0

823

RE-2X(St)HSWAH 20P0.5

20x2x0.5

0.35

1.2

16.9

0.9

1.6

21.9

920

RE-2X(St)HSWAH 24P0.5

24x2x0.5

0.35

1.2

18.3

1.25

1.6

24.0

1028

0.75mm2, Multipair

RE-2X(St)HSWAH 2P0.75

2x2x0.75

0.38

0.9

8.5

0.9

1.4

13.1

308

RE-2X(St)HSWAH 4P0.75

3x2x0.75

0.38

1.0

10.0

0.9

1.4

14.6

371

RE-2X(St)HSWAH 5P0.75

4x2x0.75

0.38

1.0

10.9

0.9

1.4

15.5

436

RE-2X(St)HSWAH 6P0.75

5x2x0.75

0.38

1.0

11.8

0.9

1.4

16.4

495

RE-2X(St)HSWAH 8P0.75

8x2x0.75

0.38

1.1

12.8

0.9

1.5

17.6

533

RE-2X(St)HSWAH 10P0.75

10x2x0.75

0.38

1.1

14.5

0.9

1.5

19.3

637

RE-2X(St)HSWAH 12P0.75

12x2x0.75

0.38

1.1

15.1

0.9

1.5

19.9

825

RE-2X(St)HSWAH 16P0.75

16x2x0.75

0.38

1.2

17.3

0.9

1.6

22.3

965

RE-2X(St)HSWAH 20P0.75

20x2x0.75

0.38

1.3

19.2

1.25

1.6

24.9

1116

RE-2X(St)HSWAH 24P0.75

24x2x0.75

0.38

1.3

20.8

1.25

1.6

26.7

1257

1.0mm2, Multipair

RE-2X(St)HSWAH 2P1.0

2x2x1.0

0.4

0.9

9.2

0.9

1.4

13.8

336

RE-2X(St)HSWAH 4P1.0

3x2x1.0

0.4

1.0

10.9

0.9

1.4

15.5

436

RE-2X(St)HSWAH 5P1.0

4x2x1.0

0.4

1.0

11.9

0.9

1.4

16.5

494

RE-2X(St)HSWAH 6P1.0

5x2x1.0

0.4

1.0

13.0

0.9

1.4

17.6

550

RE-2X(St)HSWAH 8P1.0

8x2x1.0

0.4

1.1

14.0

0.9

1.5

18.8

633

RE-2X(St)HSWAH 10P1.0

10x2x1.0

0.4

1.1

15.9

0.9

1.5

20.7

859

RE-2X(St)HSWAH 12P1.0

12x2x1.0

0.4

1.2

16.8

0.9

1.5

21.6

972

RE-2X(St)HSWAH 16P1.0

16x2x1.0

0.4

1.2

19.0

1.25

1.6

24.7

1171

RE-2X(St)HSWAH 20P1.0

20x2x1.0

0.4

1.3

21.1

1.25

1.7

27.0

1316

RE-2X(St)HSWAH 24P1.0

24x2x1.0

0.4

1.4

23.1

1.25

1.7

29.0

1520

1.3mm2, Multipair

RE-2X(St)HSWAH 2P1.3

2x2x1.3

0.45

1.0

10.4

0.9

1.4

15.0

382

RE-2X(St)HSWAH 4P1.3

3x2x1.3

0.45

1.0

12.0

0.9

1.4

16.6

510

RE-2X(St)HSWAH 5P1.3

4x2x1.3

0.45

1.1

13.4

0.9

1.5

18.2

595

RE-2X(St)HSWAH 6P1.3

5x2x1.3

0.45

1.1

14.6

0.9

1.5

19.4

657

RE-2X(St)HSWAH 8P1.3

8x2x1.3

0.45

1.2

15.7

0.9

1.5

20.5

869

RE-2X(St)HSWAH 10P1.3

10x2x1.3

0.45

1.2

17.9

0.9

1.6

23.6

1011

RE-2X(St)HSWAH 12P1.3

12x2x1.3

0.45

1.3

18.9

1.25

1.6

24.6

1110

RE-2X(St)HSWAH 16P1.3

16x2x1.3

0.45

1.3

21.4

1.25

1.7

27.3

1361

RE-2X(St)HSWAH 20P1.3

20x2x1.3

0.45

1.4

23.8

1.25

1.8

29.9

1599

RE-2X(St)HSWAH 24P1.3

24x2x1.3

0.45

1.5

25.9

1.25

1.8

32.0

1960

1.5mm2, Multipair

RE-2X(St)HSWAH 2P1.5

2x2x1.5

0.45

1.0

10.8

0.9

1.4

15.4

419

RE-2X(St)HSWAH 4P1.5

3x2x1.5

0.45

1.1

12.7

0.9

1.5

17.5

544

RE-2X(St)HSWAH 5P1.5

4x2x1.5

0.45

1.1

14.0

0.9

1.5

18.8

627

RE-2X(St)HSWAH 6P1.5

5x2x1.5

0.45

1.2

15.2

0.9

1.5

20.0

833

RE-2X(St)HSWAH 8P1.5

8x2x1.5

0.45

1.2

16.4

0.9

1.6

21.4

943

RE-2X(St)HSWAH 10P1.5

10x2x1.5

0.45

1.3

18.8

1.25

1.6

24.5

1095

RE-2X(St)HSWAH 12P1.5

12x2x1.5

0.45

1.3

19.7

1.25

1.7

25.6

1197

RE-2X(St)HSWAH 16P1.5

16x2x1.5

0.45

1.4

22.5

1.25

1.7

28.4

1511

RE-2X(St)HSWAH 20P1.5

20x2x1.5

0.45

1.5

25.0

1.25

1.8

31.1

1968

RE-2X(St)HSWAH 24P1.5

24x2x1.5

0.45

1.5

27.1

1.25

1.8

33.2

2247

Note : Other conductor sizes & core configurations are available upon request

Electrical PROPERTIES

Conductor Area Size

mm 2

0.5

0.75

1.0

1.3

1.5

Insulation thickness (nominal)

mm

0.35

0.38

0.4

0.45

0.45

Conductor resistance (20°C)

Ω/km

36.7

25

18.5

14.2

12.3

Insulation resistance (20°C)

MΩ.km(Min.)

5000

Mutual Capacitance (1 kHz)

pF/m(Max.)

         
 

up to 4 pairs

90

90

90

102

102

 

above 4 pairs

75

75

75

85

85

Capacitance unbalance(1 kHz)

pF/500 m (Max.)

500

Inductance

mH/km (Max.)

1

L / R (ratio) (max.)

μH/Ω

25

25

25

40

40

Operating voltage Urms

V

300

Test Voltage

Core to Core

V

1500

Core to Screen

V

1500