Current Ratings for Continuous Service (IEC 60092-352)
Conductor temperature |
90℃ |
|||||
Nominal cross- sectional Area (mm²) |
Single core ( A ) |
Two core ( A ) |
Three core & four core ( A ) |
|||
0.5 |
10 |
8.5 |
7 |
|||
0.75 |
13 |
11 |
9 |
|||
1 |
18 |
15 |
13 |
|||
1.5 |
23 |
20 |
16 |
|||
2.5 |
30 |
26 |
21 |
|||
4 |
40 |
34 |
28 |
|||
6 |
52 |
44 |
36 |
|||
10 |
72 |
61 |
50 |
|||
16 |
96 |
82 |
67 |
|||
25 |
127 |
108 |
89 |
|||
35 |
157 |
133 |
110 |
|||
50 |
196 |
167 |
137 |
|||
70 |
242 |
206 |
169 |
|||
95 |
293 |
249 |
205 |
|||
120 |
339 |
288 |
237 |
|||
150 |
389 |
331 |
273 |
|||
185 |
444 |
377 |
311 |
|||
240 |
522 |
444 |
366 |
|||
300 |
601 |
511 |
420 |
|||
|
d.c. |
a.c. |
d.c. |
a.c. |
d.c. |
a.c. |
400 |
690 |
670 |
587 |
570 |
483 |
469 |
500 |
780 |
720 |
663 |
612 |
546 |
504 |
500 |
890 |
780 |
757 |
663 |
623 |
546 |
Note
- Maximum permissible service temperature of the conductor is 90℃.
- The current ratings given above are based on an ambient air temperature of 45℃.
- The current ratings given above are for 6 cables of less bunched or laid together in flat formation. When more than 6 cables are bunched or laid close together, the current ratings
given above should be multiplied by correction factor 0.85.
- For cables with more than four core cables, the current ratings are calculated by the following formula.
I=I1/N1/3
I1: Current for single core cable
N: Number of cores
- Correction factors for various ambient air temperature
Maximum conductor temperature |
Correction factors for ambient air temperature |
|||||||||
℃ |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
75 |
80 |
90 |
1.10 |
1.05 |
1.00 |
0.94 |
0.88 |
0.82 |
0.74 |
0.67 |
0.58 |
0.47 |