(N)TSCGECWOEU Medium-Voltage Trailing Cable VDE 0250 Part 813

NTSCGECWOEU Medium Voltage Trailing Cable

Applications These cables are used for the connection of electrical equipment, in minesand underground excavations with hazardousenvironments under particularly high mechanical loads,e.g. high-voltage transformers on power lines inunderground mining and tunnelling.
Standards Based on VDE 0250 Part 813
Construction
Conductors Flexible stranded copper conductor, class 5 according to DIN VDE 0295.
Inner Conductor Layer Special rubber compound, conductive.
Insulation Rubber type 3GI3.
Outer Conductor Layer Special rubber compound, conductive, easy strippable.
Pilot Cores (optional) Tinned copper conductor with EPR insulation.
Earth Conductor Spiral of tinnedcopper wires.
InnerSheath Rubber type GM1b.
Monitoring Shield/Armour Braided armour of combined copper-steel wires; or wrap of copper and steel wires, copper tape in opposite direction, reinforcing tape.
Outer Sheath Rubber type 5GM5.

Dimensions and Weight

6/10kV

Number of Cores×Nominal Cross Section

Minimium Overall Diameter

Maximum Overall Diameter

Nominal Weight

No.×mm²

mm

mm

kg/km

3×25+3×16/3E+3×2.5ST+6UEL

48

52

3500

3×35+3×16/3E+3×2.5ST+6UEL

51

55

3750

3×50+3×25/3E+3×2.5ST+6UEL

56

60

4720

3×95+3×50/3E+3×2.5ST+6UEL

66

71

7260

3×120+3×70/3E+6UEL

70

75

9700

3×150+3×70/3E+6UEL

73

78

9950

 

12/20 (24) kV

Number of Cores×Nominal Cross Section

Minimium Overall Diameter

Maximum Overall Diameter

Nominal Weight

No.×mm²

mm

mm

kg/km

3×25+3×25/3E+6UEL

62

67

5800

3×95+3×50/3E+6UEL

74

78

11000

3×120+3×70/3E+6UEL

80

85

13000