UL Industrial Cables RHH/RHW, copper, 2000V

018-652-american-standard-ul-industrial-cables-rhh-rhw-copper-2000v.pdf

American Standard UL Industrial Cables RHHRHW copper 2000V

Application and Description Type RHH, RHW-2 copper wire is suitable for wiring in raceways, conduit, etc. Applications include general purpose wiring for power distribution, services, feeders, and branch circuit wiring in residential, industrial, and commercial buildings.
Cable Construction
Conductor Stranded bare annealed soft copper
Insulation Flame-retardant, abrasion, moisture and heat resistant Cross-Linked Polyetdylene (FRXLPE)
Color upon request, black is preferable
Technical Characteristics - UL 44 - Thermoset-Insulated Wires and Cables
- UL 854 - Service Entrance Cables.
- UL 1685 - UL Flame Exposure Test
- ICEA S-95-658 (NEMA WC70)

Cable Parameter

AWG OR KCMIL

STRAND

NOMINAL INSULATION THICKNESS INCH/MM

NOMINAL OVERALL DIAMETER INCH/MM

CABLE 

WEIGHT 

LBS/KFT KG/KM

14

7

0.060

1.52

0.193

4.90

25

37

12

7

0.060

1.52

0.212

5.38

34

51

10

7

0.060

1.52

0.236

5.99

48

71

8

7

0.070

1.78

0.286

7.26

73

109

6

7

0.070

1.78

0.324

8.23

106

158

4

7

0.070

1.78

0.372

9.45

158

235

3

7

0.070

1.78

0.4

10.16

195

290

2

7

0.070

1.78

0.432

10.97

240

357

1

19

0.090

2.29

0.501

12.73

310

461

1/0

19

0.090

2.29

0.54

13.72

382

568

2/0

19

0.090

2.29

0.584

14.83

472

702

3/0

19

0.090

2.29

0.634

16.10

586

872

4/0

19

0.090

2.29

0.69

17.53

728

1083

250

37

0.105

2.67

0.785

19.94

871

1296

300

37

0.105

2.67

0.839

21.31

1,033

1537

350

37

0.105

2.67

0.891

22.63

1,195

1778

400

37

0.105

2.67

0.938

23.83

1,357

2019

500

37

0.105

2.67

1.023

25.98

1,677

2495

600

61

0.120

3.05

1.131

28.73

2,021

3007

750

61

0.120

3.05

1.238

31.45

2,501

3721