German Standard Industrial Cables H05G-K/H07G-K

German Standard Industrial Cables H05G KH07G K

Application and Description These cables are recommended for tde internal wiring of switchboards and distributor boards as well as 1000V. or direct nominal voltage of 750V. These cables are all allowed for laying in tubes in and under plaster.
Standard and Approval HD 22.7 S2
VDE-0282 Part-7
CEI 20-19/7
CEI 20-35(EN60332-1)
CE Low Voltage Directive 73/23/EEC and 93/68/EEC
ROHS compliant
Cable Construction Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5
Rubber compound type EI3 (EVA) to DIN VDE 0282 part 7 insulation
Cores to VDE-0293 colors
Technical Characteristics WORKING VOLTAGE: 300/500v (H05G-K) ; 450/750v (H07G-K)
TEST VOLTAGE: 2000volts (H05G-K) ; 2500 volts (H07G-K)
FLEXING BENDING RADIUS: 7 x Ø
STATIC BENDING RADIUS: 7 x Ø
FLEXING TEMPERATURE: -25 ºC to +110 ºC
STATIC TEMPERATURE: -40 ºC to +110 ºC
FLAME RETARDANT: IEC 60332.1
INSULATION RESISTANCE: 10 MΩ x km

Cable Parameter

AWG

NO. OF CORES X NOMINAL CROSS SECTIONAL AREA

NOMINAL THICKNESS OF INSULATION

NOMINAL OVERALL DIAMETER

NOMINAL COPPER WEIGHT

NOMINAL WEIGHT

# X MM²

MM

MM

KG/KM

KG/KM

H05G-K

20(16/32)

1 x 0.5

0.6

2.3

4.8

13

18(24/32)

1 x 0.75

0.6

2.6

7.2

16

17(32/32)

1 x 1

0.6

2.8

9.6

22

H07G-K

16(30/30)

1 x 1.5

0.8

3.4

14.4

24

14(50/30)

1 x 2.5

0.9

4.1

24

42

12(56/28)

1 x 4

1.0

5.1

38

61

10(84/28)

1 x 6

1.0

5.5

58

78

8(80/26)

1 x 10

1.2

6.8

96

130

6(128/26)

1 x 16

1.2

8.4

154

212

4(200/26)

1 x 25

1.4

9.9

240

323

2(280/26)

1 x 35

1.4

11.4

336

422

1(400/26)

1 x 50

1.6

13.2

480

527

2/0(356/24)

1 x 70

1.6

15.4

672

726

3/0(485/24)

1 x 95

1.8

17.2

912

937

4/0(614/24)

1 x 120

1.8

19.7

1152

1192