0.6/1kV 3 Cores + 3 Earth Copper Tape Screened CU/XLPE/LSZH/CT/LSZH Power Cable

0.6/1kV 3 Cores + 3 Earth Copper Tape Screened CU/XLPE/LSZH/CT/LSZH Power Cable

 

CU/XLPE/LSZH/CT/LSZH (3 Cores + 3 Earth)
XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Sheathed Cable

 

Application

These power cable for fixed installations such as distribution networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.

33core insulation sheath ct sheath

Construction

Conductor: Plain annealed copper, class1 solid or class 2 stranded acc. to IEC 60228.
                 Flexible class 5 or tinned conductor could be offer upon request.
Insulation: Cross-linked polyethlene (XLPE) compound as per IEC 60502-1.
Insulation Color Code:

Number of Cores Color Code to IEC 60502-1 Color Code to BS 5467
3+3 Red, Yellow, Blue, Green/
Yellow (x3) or Others
Brown, Black, Grey, Green/
Yellow (x3)

Assembly: Cores cabled together with PP filler and covered with non-woven tape.
Bedding: Low smoke zero halogen (LSZH) compound type ST8 (90°C) of IEC 60502-1.
Bedding Colour: Black or other color as per customer request.
Armour: Copper tape.
Outer Sheath: Low smoke zero halogen (LSZH) compound type ST8 (90°C) of IEC 60502-1.
Outer Sheath Color: Black or other color as per customer request.

 

Electrical Characteristics

Recommended rated voltages U0

Highest system voltage
(Um) (kV)
Rated voltage (U0) (kV)
Categories A and B Category C
1,2 0,6 0,6

Routine test voltages

Rated voltage U0 (kV) 0,6
Test voltage (kV) 3,5

Maximum conductor temperatures for different types of insulating compound

Maximum conductor temperature (°C)
Normal operation Short-circuit (5 s maximum duration)
90 250

Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes

 

Reference Standards

Design Specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2, IEC60754-1, IEC60754-2, BS EN50267-2-1, BS EN50267-2-2

 

Installation Reference

Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 50

 

Dimension

Nominal Conductor Area(mm2) Combined Earth Size(mm2) No.and Diameter of Wires
(no./mm)
Thickness of Insulation
(mm)
Diameter Under Screen
(mm)
Overall Diameter
(mm)
Approximate Weight
(kg/km)
3x1.5 4.5(3x1.5) 7/0.53 0.7 11.7 16.8 485
3x.25 4.5(3x1.5) 7/0.67 0.7 12.3 17.4 532
3x4 4.5(3x1.5) 7/0.85 0.7 13.1 18.2 602
3x6 7.5(3x1.5) 7/1.04 0.7 14.6 19.7 734
3x10 12(3x4) 7/1.35 0.7 16.8 21.9 966
3x16 18(3x6) 7/1.70 0.7 19.2 24.3 1271
3x25 30(3x10) 7/2.14 0.9 23.2 28.3 1796
3x35 30(3x10) 7/2.52 0.9 24.9 30 2131
3x50 30(3x10) 19/1.78 1 27.4 32.7 2743
3x70 48(3x16) 19/2.14 1.1 32.4 37.9 3763
3x95 48(3x16) 19/2.52 1.1 35.2 40.9 4658
3x120 75(3x25) 37/2.03 1.2 40.9 46.4 5905
3x150 75(3x25) 37/2.25 1.4 43.8 49.9 6919
3x185 105(3x35) 37/2.52 1.6 49 55.5 8584
3x240 150x(3x50) 61/2.25 1.7 56.3 63.4 11343
3x300 150x(3x50) 61/2.52 1.8 60.3 67.6 13373

 

downloadpdf