4 Core Copper Tape Screened CU/XLPE/LSZH/CT/LSZH Power Cable to IEC 60502

4 Core Copper Tape Screened CU/XLPE/LSZH/CT/LSZH Power Cable to IEC 60502

 

CU/XLPE/LSZH/CT/LSZH (4 Cores)
XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Sheathed Cable

 

Application

These power cable for fixed installations such as distribution networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.

 4core insulation sheath ct sheath

Construction

Conductor: Plain annealed copper, class1 solid or class 2 stranded acc. to IEC 60228.
                 Flexible class 5 or tinned conductor could be offer upon request.
Insulation: Cross-linked polyethlene (XLPE) compound as per IEC 60502-1.
Insulation Color Code:

Number of Cores Color Code to IEC 60502-1 Color Code to BS 5467
4 Red, Yellow, Blue, Black Brown, Black, Grey, Blue

Assembly: Cores cabled together with PP filler and covered with non-woven tape.
Bedding: Low smoke zero halogen (LSZH) compound type ST8 (90°C) of IEC 60502-1.
Bedding Colour: Black or other color as per customer request.
Armour: Copper tape.
Outer Sheath: Low smoke zero halogen (LSZH) compound type ST8 (90°C) of IEC 60502-1.
Outer Sheath Color: Black or other color as per customer request.

 

Electrical Characteristics

Recommended rated voltages U0

Highest system voltage
(Um) (kV)
Rated voltage (U0) (kV)
Categories A and B Category C
1,2 0,6 0,6

Routine test voltages

Rated voltage U0 (kV) 0,6
Test voltage (kV) 3,5

Maximum conductor temperatures for different types of insulating compound

Short-circuit (5 s maximum duration)​

Maximum conductor temperature (°C)  
 Normal operation Short-circuit (5 s maximum duration) 
 90  250

Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes

 

Reference Standards

Design Specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-3-22, BS EN60332-3-22
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2, IEC60754-1, IEC60754-2, BS EN50267-2-1, BS EN50267-2-2

 

Installation Reference

Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 50

 

Dimension

Nominal Conductor Area(mm2) No.and Diameter of Wires
(no./mm)
Thickness of Insulation
(mm)
Diameter Under Screen
(mm)
Overall Diameter
(mm)
Approximate Weight
(kg/km)
4x1.5 7/0.53 0.7 9.7 14.4 371
4x2.5 7/0.67 0.7 10.7 15.4 441
4x4 7/0.85 0.7 12 16.7 544
4x6 7/1.04 0.7 13.4 18.1 668
4x10 7/1.35 0.7 15.6 20.3 907
4x16 7/1.70 0.7 18.2 22.9 1229
4x25 7/2.14 0.9 22.3 27 1770
4x35 7/2.52 0.9 25.1 29.8 2264
4x50 19/1.78 1 25.4 30.3 2721
4x70 19/2.14 1.1 29.8 34.9 3734
4x95 19/2.52 1.1 33.5 39 5069
4x120 37/2.03 1.2 37.3 43 6254
4x150 37/2.25 1.4 42.8 48.9 7622
4x185 37/2.52 1.6 47.4 53.7 9333
4x240 61/2.25 1.7 54.7 61.8 12296
4x300 61/2.52 1.8 60.6 67.9 15030

 

downloadpdf