Application
These power cable for fixed installations such as distribution networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.
Construction
1 Conductor: Plain annealed copper, class1 solid or class 2 stranded acc. to IEC 60228. Flexible class 5 or tinned conductor could be offer upon request.
2 Insulation: Cross-linked polyethylene (XLPE) compound as per IEC 60502-1. Insulation Color Code:
Number of Cores | Color Code to IEC 60502-1 | Color Code to BS 5467 |
1 | Natural |
3 Outer Sheath: Polyvinyl choride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1.
Outer Sheath Color: Black or other color as per customer request.
Electrical Characteristics
Recommended rated voltages U0
Highest system voltage | Rated voltage (U0) (kV) | ||||
(Um) (kV) | Categories A and B | Category C | |||
1,2 | 0,6 | 0,6 | |||
Routine test voltages | |||||
Rated voltage U0 (kV) | 0,6 | ||||
Test voltage (kV) | 3,5 | ||||
Maximum conductor temperatures for different types of insulating compound | |||||
Maximum conductor temperature (°C) | |||||
Normal operation | Short-circuit (5 s maximum duration) | ||||
90 | 250 |
Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes
Installation Reference
Min .Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 50
References Standards
Design Specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1