Application
These power cable for fixed installations such as distribution networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and air-conditioning systems; Power stations; Stage applications etc.

Construction
| 1 | Conductor: Plain annealed copper, class1 solid or class 2 stranded as per IEC 60228. | ||||
| Flexible class 5 or tinned conductor could be offer upon request. | |||||
| 2 | Insulation: Cross-linked polyethylene (XLPE) compound as per IEC 60502-1. | ||||
| Insulation Colour: | |||||
| Number of Cores | Color Code to IEC 60502-1 | Color Code to BS 5467 | |||
| 2 | Red & Black | Brown & Blue | |||
| 3 | Red, Yellow and Blue | Brown, Black and Grey | |||
| 4 | Red, Yellow, Blue and Black | Blue, Brown, Black and Grey | |||
| 5 | Red, Yellow, Blue, Black and | Green / Yellow, Blue, Brown, | |||
| Green / Yellow | Black and Grey | ||||
| Assembly: Cores cabled together with PP filler and covered with non-woven tape. | |||||
| 3 | Outer Sheath: Polyvinyl chloride (PVC) compound type ST1 (80°C), ST2 (90°C) of IEC 60502-1. | ||||
| Outer Sheath Colour: Black or other color as per customer request. | |||||
Electrical Characteristics
Recommended rated voltages U0
| Highest system voltage | Rated voltage (U0) (kV) | ||||
| (Um) (kV) | Categories A and B | Category C | |||
| 1,2 | 0,6 | 0,6 | |||
| Routine test voltages | |||||
| Rated voltage U0 (kV) | 0,6 | ||||
| Test voltage (kV) | 3,5 | ||||
| Maximum conductor temperatures for different types of insulating compound | |||||
| Maximum conductor temperature (°C) | |||||
| Normal operation | Short-circuit (5 s maximum duration) | ||||
| 90 | 250 | ||||
Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes
Installation Reference
Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 50
Reference Standards
Design Specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC60332-1, BS EN60332-1