LI HCH FE180 (PH30) (CU/SR/OS/LSZH 300/500V Class 5)
Application: |
The cables are designed for indoor instrumentation and control cabling, electrically noisy environments and fire alarm systems in office buildings. |
STANDARDS: |
Basic design to VDE 0812/EN 50290-2-27 |
FIRE PERFORMANCE
Circuit Integrity |
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
Circuit Integrity with mechanical shock |
EN 50200(PH30); CEI 20-36/4-0 |
Circuit Integrity with mechanical shock & water spray |
EN 50200 annex E |
System circuit integrity |
DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
300/500 V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
Cabling: The insulated cores are cabled in concentric layers with suitable non-hygroscopic fillers.
Fire Barrier: Polyester tape + fiber glass tape
Overall screen: Aluminum/polyester tape with tinned copper braid (min. 85% Coverage)
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH
compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation Colour: Per VDE 0812
Sheath Colour: Orange (other colours on request)
TYPE CODE
LI Equipment cable with fine stranded conductor
H Halogen free ceramic polymer compound
C Copper Wire Braid
FE180 Insulation integrity (950°C 180 minutes)
PH 90 Fire Test for 90 mins at 830°C
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 7.5 x Overall Diameter
Electrical PROPERTIES
Dielectric test: |
2000 V r.m.s. x 5' (core/core) |
Insulation resistance |
≥300 MΩ x km (at 20°C); |
Short circuit temperature |
350°C |
CONSTRUCTION PARAMETERS
Cable Code |
No. of Core X Cross Section |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Nominal Overall Diameter |
Approx. Weight |
|
mm2 |
mm |
mm |
mm |
kg/km |
2 cores |
|||||
LI-HCH FE180 (PH30) |
2x0.75 |
0.6 |
0.8 |
6.3 |
55 |
LI-HCH FE180 (PH30) |
2x1.0 |
0.6 |
0.9 |
6.9 |
62 |
LI-HCH FE180 (PH30) |
2x1.5 |
0.7 |
0.9 |
7.3 |
79 |
3 cores |
|||||
LI-HCH FE180 (PH30) |
3x0.75 |
0.6 |
0.8 |
6.6 |
67 |
LI-HCH FE180 (PH30) |
3x1.0 |
0.6 |
0.9 |
7.2 |
77 |
LI-HCH FE180 (PH30) |
3x1.5 |
0.7 |
0.9 |
7.6 |
101 |
4 cores |
|||||
LI-HCH FE180 (PH30) |
4x0.75 |
0.6 |
0.9 |
7.2 |
85 |
LI-HCH FE180 (PH30) |
4x1.0 |
0.6 |
1.0 |
7.7 |
98 |
LI-HCH FE180 (PH30) |
4x1.5 |
0.7 |
1.0 |
8.2 |
112 |
5 cores |
|||||
LI-HCH FE180 (PH30) |
5x0.75 |
0.6 |
0.9 |
7.9 |
105 |
LI-HCH FE180 (PH30) |
5x1.0 |
0.6 |
1.0 |
7.9 |
117 |
LI-HCH FE180 (PH30) |
5x1.5 |
0.7 |
1.0 |
9.0 |
127 |
6 cores |
|||||
LI-HCH FE180 (PH30) |
6x0.75 |
0.6 |
0.9 |
8.6 |
121 |
LI-HCH FE180 (PH30) |
6x1.0 |
0.6 |
1.0 |
9.1 |
138 |
LI-HCH FE180 (PH30) |
6x1.5 |
0.7 |
1.0 |
10.0 |
161 |
7 cores |
|||||
LI-HCH FE180 (PH30) |
7x0.75 |
0.6 |
0.9 |
8.6 |
131 |
LI-HCH FE180 (PH30) |
7x1.0 |
0.6 |
1.0 |
9.1 |
152 |
LI-HCH FE180 (PH30) |
7x1.5 |
0.7 |
1.1 |
10.0 |
193 |
Note : Other conductor sizes & core configurations are available upon request.