PE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Single Triple)

RE-2Y(St)HSWAH 70°C / 300 V

PE Insulated LSZH Sheathed Overall Screened Armoured Instrumentation Cables Single Triple

STANDARDS  Basic design to EN50288-7
APPLICATION:  These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petr°Chemistry industry plants, power plants, natural gas and petroluem plants, etc...
These cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Sunlight Resistance

UL 1581 section 1200

Oil Resistance

ICEA S-73-532**

Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of tensite strength/min. 60% of elongation.

VOLTAGE RATING  300V
CABLE CONSTRUCTION  
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: PE compound, EN 50290. 2-23.
Pair: Two conductors twisted to form a pair
Lay-up: Pairs laid up in layers of optimum pitch
Separator: Polyester tape
Overall Screen:  Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: LSZH compound, EN 50290-2-27
Armour:  Galvenized round steel wire, EN 10257-1
Outer Sheath:  Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE  
Insulation:  Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.
Outer Sheath:  Black or blue for intrinsically safe systems
Physical AND THERMAL PROPERTIES  
Temperature Range During Operation (Fixed State):  -30°C – +70°C
Temperature Range During Installation (Mobile State):  -5°C – +50°C
Minimum Bending Radius:  10 X Overall Diameter

CONSTRUCTION PARAMETERS

Cable Code

RE-2Y(St)HSWAH

No. of Triples 

x3xCross Section

Nominal 

Insulation 

Thick- 

ness

Nominal 

Inner 

Sheath 

Thick-ness

Nominal Overall 

Diameter 

Over 

Inner 

Sheath

Nominal 

Armour 

Wire 

Diameter

Nominal 

Outer 

Sheath 

Thick-ness

Nominal Overall Diameter

Approx. 

Weight

 

No.x3xmm2

mm

mm

mm

mm

mm

mm

kg/km

RE-2Y(St)HSWAH 1T0.5

1x3x0.50

0.35

0.8

5.4

0.9

1.3

9.8

200

RE-2Y(St)HSWAH 1T0.75

1x3x0.75

0.38

0.9

6.1

0.9

1.3

10.5

220

RE-2Y(St)HSWAH 1T1.0

1x3x1.0

0.4

0.9

6.6

0.9

1.3

11.0

244

RE-2Y(St)HSWAH 1T1.3

1x3x1.3

0.45

0.9

7.2

0.9

1.3

11.6

268

RE-2Y(St)HSWAH 1T1.5

1x3x1.5

0.45

0.9

7.5

0.9

1.3

11.9

277

Note : Other conductor sizes & core configurations are available upon request

Electrical PROPERTIES

Conductor Area Size

mm 2

0.5

0.75

1.0

1.3

1.5

Insulation thickness (nominal)

mm

0.35

0.38

0.4

0.45

0.45

Conductor resistance (20°C)

Ω/km

36.7

25

18.5

14.2

12.3

Insulation resistance (20°C)

MΩ.km(Min.)

5000

Mutual Capacitance (1 kHz)

pF/m(Max.)

115

Capacitance unbalance(1 kHz)

pF/500 m (Max.)

500

L / R (ratio) (max.)

μH/Ω

25

25

25

40

40

Inductance

mH/km(Max.)

1

1

1

1

1

Operating voltage Urms

V

300

Test Voltage

Core to Core

V

1500

Core to Screen

V

1500