PE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Multitriple)

RE-2Y(St)HSWAH 70°C / 300 V

PE Insulated LSZH Sheathed Overall Screened Armoured Instrumentation Cables Multitriple

STANDARDS  Basic design to EN50288-7
APPLICATION:  These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petr°Chemistry industry plants, power plants, natural gas and petroluem plants, etc...
These cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet l°Cations; on racks, trays, in conduits.

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);  

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation   (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;  

CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;  

CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;  

CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Sunlight Resistance

UL 1581 section 1200

Oil Resistance

ICEA S-73-532**

Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of tensite strength/min.60% of elongation.

VOLTAGE RATING 300V
CABLE CONSTRUCTION   
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: PE compound, EN 50290. 2-23.
Pair: Two conductors twisted to form a pair 
Lay-up: Pairs laid up in layers of optimum pitch
Separator: Polyester tape
Overall Screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: HFFR compound, EN 50290-2-27 
Armour:  Galvenized round steel wire, EN 10257-1
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE  
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples. 
Outer Sheath:  Black or blue for intrinsically safe systems
Physical AND THERMAL PROPERTIES  
Temperature Range During Operation (Fixed State):  -30°C – +70°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius:  10 X Overall Diameter

CONSTRUCTION PARAMETERS

Cable Code

RE-2Y(St)HSWAH

No. of Triples 

x3xCross Section

Nominal 

Insulation 

Thick-ness

Nominal 

Inner Sheath 

Thick 

-ness

Nominal Overall  

Diameter  

Over 

Inner   

Sheath

Nominal 

Armour  

Wire  

Diameter

Nominal 

Outer 

Sheath 

Thick-ness

Nominal Overall Diameter

Approx.  

Weight

 

No.x3xmm2

mm

mm

mm

mm

mm

mm

kg/km

0.5mm2, Multitriple 

RE-2Y(St)HSWAH 2T0.5

2x3x0.5

0.35

0.9

8.4

0.9

1.4

13.0

326

RE-2Y(St)HSWAH 4T0.5

4x3x0.5

0.35

1.0

9.8

0.9

1.4

14.4

386

RE-2Y(St)HSWAH 5T0.5

5x3x0.5

0.35

1.0

10.8

0.9

1.4

15.4

454

RE-2Y(St)HSWAH 6T0.5

6x3x0.5

0.35

1.0

12.1

0.9

1.4

16.7

513

RE-2Y(St)HSWAH 8T0.5

8x3x0.5

0.35

1.1

13.1

0.9

1.5

17.9

571

RE-2Y(St)HSWAH 10T0.5

10x3x0.5

0.35

1.1

14.7

0.9

1.5

19.5

677

RE-2Y(St)HSWAH 12T0.5

12x3x0.5

0.35

1.1

15.2

0.9

1.5

20.0

845

RE-2Y(St)HSWAH 16T0.5

16x3x0.5

0.35

1.2

17.4

0.9

1.6

22.4

1031

RE-2Y(St)HSWAH 20T0.5

20x3x0.5

0.35

1.2

19.1

1.25

1.6

24.8

1179

RE-2Y(St)HSWAH 24T0.5

24x3x0.5

0.35

1.3

20.9

1.25

1.7

26.8

1330

0.75mm2, Multitriple 

RE-2Y(St)HSWAH 2T0.75

2x3x0.75

0.38

1.0

10.6

0.9

1.4

13.9

370

RE-2Y(St)HSWAH 4T0.75

4x3x0.75

0.38

1.1

12.4

0.9

1.4

15.5

462

RE-2Y(St)HSWAH 5T0.75

5x3x0.75

0.38

1.1

13.7

0.9

1.4

16.6

526

RE-2Y(St)HSWAH 6T0.75

6x3x0.75

0.38

1.1

15.4

0.9

1.5

18.5

615

RE-2Y(St)HSWAH 8T0.75

8x3x0.75

0.38

1.2

16.7

0.9

1.5

19.5

698

RE-2Y(St)HSWAH 10T0.75

10x3x0.75

0.38

1.3

19.0

0.9

1.5

21.5

947

RE-2Y(St)HSWAH 12T0.75

12x3x0.75

0.38

1.3

19.7

0.9

1.7

22.3

1029

RE-2Y(St)HSWAH 16T0.75

16x3x0.75

0.38

1.4

22.5

1.25

1.6

25.4

1240

RE-2Y(St)HSWAH 20T0.75

20x3x0.75

0.38

1.5

24.9

1.25

1.7

27.6

1446

RE-2Y(St)HSWAH 24T0.75

24x3x0.75

0.38

1.6

27.2

1.25

1.7

29.6

1632

1.0mm2, Multitriple 

RE-2Y(St)HSWAH 2T1.0

2x3x1

0.4

1.0

11.5

0.9

1.4

15.0

412

RE-2Y(St)HSWAH 4T1.0

4x3x1

0.4

1.1

13.4

0.9

1.4

16.5

529

RE-2Y(St)HSWAH 5T1.0

5x3x1

0.4

1.1

14.8

0.9

1.5

18.0

620

RE-2Y(St)HSWAH 6T1.0

6x3x1

0.4

1.2

16.9

0.9

1.5

19.8

830

RE-2Y(St)HSWAH 8T1.0

8x3x1

0.4

1.2

18.1

0.9

1.5

20.9

946

RE-2Y(St)HSWAH 10T1.0

10x3x1

0.4

1.3

20.7

0.9

1.6

24.1

1105

RE-2Y(St)HSWAH 12T1.0

12x3x1

0.4

1.3

21.4

1.25

1.6

24.7

1215

RE-2Y(St)HSWAH 16T1.0

16x3x1

0.4

1.4

24.4

1.25

1.7

27.6

1482

RE-2Y(St)HSWAH 20T1.0

20x3x1

0.4

1.5

27.1

1.25

1.7

30.0

1740

RE-2Y(St)HSWAH 24T1.0

24x3x1

0.4

1.6

29.6

1.25

1.8

32.2

2202

1.3mm2, Multitriple 

RE-2Y(St)HSWAH 2T1.3

2x3x1,3

0.45

1.1

12.8

0.9

1.4

16.1

463

RE-2Y(St)HSWAH 4T1.3

4x3x1,3

0.45

1.1

14.7

0.9

1.5

18.2

621

RE-2Y(St)HSWAH 5T1.3

5x3x1,3

0.45

1.2

16.5

0.9

1.5

19.6

721

RE-2Y(St)HSWAH 6T1.3

6x3x1,3

0.45

1.3

18.8

0.9

1.5

21.7

979

RE-2Y(St)HSWAH 8T1.3

8x3x1,3

0.45

1.3

20.1

0.9

1.6

23.8

1105

RE-2Y(St)HSWAH 10T1.3

10x3x1,3

0.45

1.4

23.0

1.25

1.7

26.6

1322

RE-2Y(St)HSWAH 12T1.3

12x3x1,3

0.45

1.5

24.0

1.25

1.7

27.3

1456

RE-2Y(St)HSWAH 16T1.3

16x3x1,3

0.45

1.6

27.4

1.25

1.8

30.5

1788

RE-2Y(St)HSWAH 20T1.3

20x3x1,3

0.45

1.7

30.4

1.25

1.8

33.2

2327

RE-2Y(St)HSWAH 24T1.3

24x3x1,3

0.45

1.8

33.1

1.60

1.9

36.6

2637

1.5mm2, Multitriple 

RE-2Y(St)HSWAH 2T1.5

2x3x1,5

0.45

1.1

13.2

0.9

1.4

16.5

518

RE-2Y(St)HSWAH 4T1.5

4x3x1,5

0.45

1.2

15.4

0.9

1.5

18.8

674

RE-2Y(St)HSWAH 5T1.5

5x3x1,5

0.45

1.2

17.1

0.9

1.5

20.2

869

RE-2Y(St)HSWAH 6T1.5

6x3x1,5

0.45

1.3

19.5

0.9

1.6

22.6

1049

RE-2Y(St)HSWAH 8T1.5

8x3x1,5

0.45

1.4

21.1

1.25

1.6

24.8

1210

RE-2Y(St)HSWAH 10T1.5

10x3x1,5

0.45

1.5

24.1

1.25

1.7

27.5

1435

RE-2Y(St)HSWAH 12T1.5

12x3x1,5

0.45

1.5

24.9

1.25

1.7

28.4

1569

RE-2Y(St)HSWAH 16T1.5

16x3x1,5

0.45

1.6

28.4

1.25

1.8

31.8

2162

RE-2Y(St)HSWAH 20T1.5

20x3x1,5

0.45

1.7

31.6

1.25

1.9

34.9

2515

RE-2Y(St)HSWAH 24T1.5

24x3x1,5

0.45

1.8

34.4

1.60

2.0

38.3

2879

Note : Other conductor sizes & core configurations are available upon request

Electrical PROPERTIES

Conductor Area Size 

 mm 2  

0.5 

0.75  

1.0  

1.3

1.5  

Insulation thickness (nominal)

mm

0.35

0.38

0.4

0.45

0.45

Conductor resistance (20°C) 

 Ω/km 

36.7

25

18.5

14.2

12.3

Insulation resistance (20°C)

MΩ.km(Min.)

5000

Mutual Capacitance (1 kHz) 

pF/m(Max.)

 

 

≤ 4 pairs

90

90

90

102

102

 

all other pairs

75

75

75

85

85

Capacitance unbalance(1 kHz) 

pF/500 m (Max.)

500 

L / R (ratio) (max.)

μH/Ω

25

25

25

40

40

Inductance

mH/km(Max.)

1

Operating voltage Urms

V

300

Test Voltage 

Core to Core 

1500  

Core to Screen 

1500