Applications | These heavy duty cables are designed for applications such as longwall shearers, continuous miners and mobile equipment such as shovels, dredges and drills. |
Standards | ICEA S-75-381/NEMA WC 58 ASTM B 172 ASTM B 33 CAN/CSA C22.2 No. 96 |
Construction | |
Conductors | Stranded annealed tinned copper conductor. |
Conductor Shield | Semi-conducting layer. |
Insulation | Ethylene Propylene Rubber (EPR). |
Insulation Shield | Conducting tape + Tinned copper/textile braid. |
Ground Check Conductor | Tinned copper with a yellow polypropylene insulation. |
Grounding Conductor | Tinned copper conductor. |
Jacket | Reinforced extra-heavy-duty Chlorinated Polyethylene (CPE), black. |
Options | Other jacket materials such as CSP/PCP/NBR/PVC are available upon request. Two-layer jacket with reinforcing fibre between the two layers can be offered as an option. |
Mechanical and Thermal Properties | Minimum Bending Radius: 8×OD Maximum Operating Temperature: +90℃ |
Dimensions and Weight:
Construction |
No. of Strands |
Grounding Conductor Size |
Ground Check Conductor Size |
Nominal Insulation Thickness |
Nominal Jacket Thickness |
Nominal Overall Diameter |
Nominal Weight |
Ampacity |
||||
No. of cores×AWG/kcmil |
- |
AWG/kcmil |
AWG/kcmil |
inch |
mm |
inch |
mm |
inch |
mm |
lbs/kft |
kg/km |
A |
3×2 |
259 |
6 |
8 |
0.210 |
5.3 |
0.235 |
6.0 |
2.41 |
61.2 |
3572 |
5529 |
164 |
3×1 |
259 |
5 |
8 |
0.210 |
5.3 |
0.235 |
6.0 |
2.52 |
64.0 |
4060 |
6042 |
187 |
3×1/0 |
259 |
4 |
8 |
0.210 |
5.3 |
0.250 |
6.4 |
2.64 |
67.0 |
4495 |
6927 |
215 |
3×2/0 |
329 |
3 |
8 |
0.210 |
5.3 |
0.250 |
6.4 |
2.73 |
69.3 |
5010 |
7783 |
246 |
3×3/0 |
413 |
2 |
8 |
0.210 |
5.3 |
0.265 |
6.7 |
2.90 |
73.7 |
5995 |
8922 |
283 |
3×4/0 |
532 |
1 |
8 |
0.210 |
5.3 |
0.265 |
6.7 |
3.05 |
77.5 |
6860 |
10209 |
325 |
Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.