Type SHD-GC Three-Conductor Round Portable Power Cable, CPE Jacket 15kV ICEA S-75-381

Type SHD GC Three Conductor Round Portable Power Cable CPE Jacket 15kV

Applications These heavy duty cables are designed for applications such as longwall shearers, continuous miners and mobile equipment such as shovels, dredges and drills.
Standards ICEA S-75-381/NEMA WC 58
ASTM B 172
ASTM B 33
CAN/CSA C22.2 No. 96
Construction
Conductors Stranded annealed tinned copper conductor.
Conductor Shield Semi-conducting layer.
Insulation Ethylene Propylene Rubber (EPR).
Insulation Shield Conducting tape + Tinned copper/textile braid.
Ground Check Conductor Tinned copper with a yellow polypropylene insulation.
Grounding Conductor Tinned copper conductor.
Jacket Reinforced extra-heavy-duty Chlorinated Polyethylene (CPE), black.
Options Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.
Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.
Mechanical and Thermal Properties Minimum Bending Radius: 8×OD
Maximum Operating Temperature: +90℃

Dimensions and Weight:

Construction

No. of Strands

Grounding Conductor Size

Ground Check Conductor Size

Nominal Insulation Thickness

Nominal

Jacket

Thickness

Nominal

Overall

Diameter

Nominal Weight

Ampacity

No. of cores×AWG/kcmil

-

AWG/kcmil

AWG/kcmil

inch

mm

inch

mm

inch

mm

lbs/kft

kg/km

A

3×2

259

6

8

0.210

5.3

0.235

6.0

2.41

61.2

3572

5529

164

3×1

259

5

8

0.210

5.3

0.235

6.0

2.52

64.0

4060

6042

187

3×1/0

259

4

8

0.210

5.3

0.250

6.4

2.64

67.0

4495

6927

215

3×2/0

329

3

8

0.210

5.3

0.250

6.4

2.73

69.3

5010

7783

246

3×3/0

413

2

8

0.210

5.3

0.265

6.7

2.90

73.7

5995

8922

283

3×4/0

532

1

8

0.210

5.3

0.265

6.7

3.05

77.5

6860

10209

325

Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.