XLPE Insulated 6.35/11KV & 12.7/22KV AS/NZS 1972/1125/3808

XLPE Insulated 6.3511KV 12.722KV

Applications These cables are used as HV feeder cables in fixed conditions.
Standards AS/NZS 1972:2006
AS/NZS 1125
AS/NZS 3808
Construction
Conductors Stranded plain copper conductor.
Insulation XLPE.
Individual Screen (earth conductor) Copper wire.
Inner Sheath PVC sheath.
Armour Galvanized steel wire armour.
Outer Sheath PVC sheath to AS/NZS 1429.1.

Dimensions and Weight

Nominal Conductor Area

Nominal Conductor Diameter

Insulation Thickness

Core screen

Armour Wire Diameter

Nominal Sheath Thickness

Nominal Overall Diameter

Nominal Weight

Strand Size

Area 

of Screen

mm²

mm

mm

mm

mm²

mm

mm

mm

kg/100m

6.35/11kV

16

4.8

3.4

10/0.85

5.7

2.00

2.4

46.6

330

25

5.8

3.4

10/0.85

5.7

2.50

2.5

50.1

415

35

6.8

3.4

11/0.85

6.2

2.50

2.6

52.8

475

50

8.0

3.4

15/0.85

8.5

2.50

2.7

55.7

540

70

9.6

3.4

21/0.85

11.9

2.50

2.8

59.6

645

95

11.5

3.4

29/0.85

16.5

2.50

2.9

63.9

775

120

13.1

3.4

36/0.85

20.4

2.50

3.1

67.9

905

150

14.5

3.4

44/0.85

25.0

2.50

3.2

71.5

1030

185

16.1

3.4

22/1.35

31.5

3.15

3.3

78.6

1280

240

18.5

3.4

29/1.35

41.5

3.15

3.5

84.7

1550

300

20.7

3.4

37/1.35

53.0

3.15

3.7

90.4

1820

400

23.6

3.4

47/1.35

67.3

3.15

4.0

97.9

2230

12.7/22kV

35

6.8

5.5

14/0.85

7.9

2.5

2.9

63.2

600

50

8.0

5.5

15/0.85

8.5

2.5

3.0

66.0

665

70

9.6

5.5

21/0.85

11.9

2.5

3.1

69.9

775

95

11.5

5.5

29/0.85

16.5

2.5

3.3

74.4

920

120

13.1

5.5

36/0.85

20.4

3.15

3.4

79.5

1140

150

14.5

5.5

44/0.85

25.0

3.15

3.5

83.1

1280

185

16.1

5.5

22/1.35

31.5

3.15

3.7

89.1

1450

240

18.5

5.5

29/1.35

41.5

3.15

3.9

95.0

1720

300

20.7

5.5

37/1.35

53.0

3.15

4.1

101.1

2010

400

23.6

5.5

47/1.35

67.3

3.15

4.3

108.2

2420