UL Industrial Cables AL-XHHW-2 Power Cable, CT Rated

American Standard UL Industrial Cables AL XHHW 2 Power Cable CT Rated

Application and Description Type XHHW-2 conductors are primarily used in conduit or recognized raceways for services, feeders, and branch circuit wiring as specified in the National Electrical Code 1 . XHHW-2 conductors may be used in wet or dry locations at temperatures not to exceed 90°C
Cable Construction
Conductor Single core, stranded aluminum alloy conductor
Insulation Flame-retardant, abrasion, heat, moisture and sunlight resistant Cross-Linked Polyetdylene (FRXLPE)
Color upon request, black is preferable
Technical Characteristics - UL 44 - Thermoset-Insulated Wires and Cables.
- UL - 1581 Flame Exposure Test (VW-1)
- UL 1685 - CT Flame Exposure Test.
- IEEE 1202/FT4 (2/0 AWG and larger)
- ICEA S-95-658 (NEMA WC 70) construction requirements

Cable Parameter

AWG OR KCMIL

STRAND

NOMINAL INSULATION THICKNESS INCH/MM

NOMINAL OVERALL DIAMETER INCH/MM

CABLE WEIGHT 

LBS/KFT KG/KM

1/0

10

0.055

1.40

0.449

11.40

138

205

2/0

12

0.055

1.40

0.489

12.42

171

254

3/0

16

0.055

1.40

0.536

13.61

209

311

4/0

19

0.055

1.40

0.588

14.94

253

376

250

22

0.065

1.65

0.653

16.59

304

452

350

35

0.065

1.65

0.749

19.02

410

610

400

35

0.065

1.65

0.792

20.12

463

689

500

35

0.065

1.65

0.869

22.07

567

844

600

58

0.080

2.03

0.976

24.79

695

1034

750

58

0.080

2.03

1.071

27.20

851

1266

1000

58

0.080

2.03

1.223

31.06

1110

1651