Application and Description | XHHW/PVC conductors are primarily used in conduit, cable tray or otder recongnized raceways for services, feeders, and branch circuit wiring as specified in tde National Electrical Code. XHHW/PVC conductors are sunlight resistant and may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating for XHHW/PVC conductors is 600 volts |
Cable Construction | |
Conductor | Single copper conductor, stranded tinned annealed copper per ASTM B3 Class B stranding per ASTM B8 |
Insulation | Flame-retardant, abrasion, heat, moisture and sunlight resistant Cross-Linked Polyetdylene (FRXLPE) |
Jacket | Flame retardant, moisture and sunlight resistant PVC |
Color | upon request, black is preferable |
Technical Characteristics | - UL 44 - Thermoset-Insulated Wires and Cables. - UL 1685 - UL CT Flame Exposure Test. - UL 1581 - UL Flame Exposure Test (VW-1) - IEEE 383 (IEEE 1202/FT4 (2/0 AWG and larger) - Flame Test (70,000 Btu/hr Vertical Tray Test)). - ICEA S-95-658 (NEMA WC70) |
Cable Parameter
AWG OR KCMIL |
STRAND |
NOMINAL INSULATION THICKNESS INCH/MM |
NOMINAL JACKET THICKNESS INCH/MM |
NOMINAL OVERALL DIAMETER INCH/MM |
CABLE WEIGHT LBS/KFT KG/KM |
||||
1/0 |
19 |
0.055 |
1.40 |
0.045 |
1.14 |
0.565 |
14.3 |
412 |
613 |
2/0 |
19 |
0.055 |
1.40 |
0.045 |
1.14 |
0.608 |
15.4 |
505 |
751 |
3/0 |
19 |
0.055 |
1.40 |
0.045 |
1.14 |
0.659 |
16.7 |
623 |
927 |
4/0 |
19 |
0.055 |
1.40 |
0.045 |
1.14 |
0.715 |
18.1 |
769 |
1145 |
250 |
37 |
0.065 |
1.65 |
0.065 |
1.65 |
0.821 |
20.8 |
934 |
1390 |
350 |
37 |
0.065 |
1.65 |
0.065 |
1.65 |
0.924 |
23.4 |
1268 |
1887 |
500 |
37 |
0.065 |
1.65 |
0.065 |
1.65 |
1.053 |
26.7 |
1763 |
2624 |
750 |
61 |
0.080 |
2.03 |
0.065 |
1.65 |
1.261 |
32.0 |
2602 |
3871 |
1000 |
61 |
0.080 |
2.03 |
0.065 |
1.65 |
1.41 |
35.8 |
3411 |
5076 |